Installation Instructions

 

(cont.)

-6-

3. Connect the cable to the Indoor unit

Electrical Work 

Electric safety regulations for the initial installation:

•  If there are any safety concerns with the electrical power supply, the technician should consult a certified electrician 

and have the problem resolved before installing the unit.

•  Power voltage should be in the range of 90%~110% of rated voltage.
•  The circuit breaker at the electrical panel should be no more than 1.5 times the max current of the outdoor unit. All 

the electrical information is located on the reverse side of the electrical cover on the outdoor unit. Follow all local and 

national electric codes.

•  Each outdoor unit must have its won circuit breaker.
•  Install the proper sized electrical wire from the circuit breaker located at the electrical panel to an outdoor 

weatherproof disconnect.

•  The outdoor unit must be grounded per code. If the unit is not grounded it will not operate per system specifications.
•  Install a liquid tight electrical whip from the outdoor disconnect to the outdoor unit.
•  All wiring must comply with local and national codes and be installed by a certified electrician.

Suggested Minimum Wire Size 

(AWG: American Wire Gauge)

Appliance 

Amps

AWG Wire 

Size

10

18

13

16

18

14

25

12

30

10

NOTE:

  

The cable size and the current of the 

fuse or switch are determined by the 

maximum current indicated on the 

nameplate, which is located on the side 

panel of the unit. Please refer to the 

nameplate before selecting the cable, 

fuse and switch.

Connect the Cable to the Indoor Unit

NOTE: 

Before performing any electrical work, turn off the power at the main 

panel to the unit.

•  The inside and outside connecting cable can be connected without 

removing the front grille.

•  Lift the indoor unit panel up; remove the electrical box cover by loosening 

the screw.

•  Ensure the color of wires of outdoor unit and the terminal numbers are the 

same to the indoor units respectively.

•  Wrap those cables not connected with terminals with insulation tape so that 

they will not touch any electrical components. Secure the cable onto the 

control board with the cord clamp.

Terminal block of indoor unit

Electrical box

cover

Front Panel

To outdoor unit

To outdoor unit

Cord clamp

L1  L2    S

L1  L2    S

or

Terminal block of indoor unit

Electrical box

cover

Front Panel

To outdoor unit

To outdoor unit

Cord clamp

L1  L2    S

L1  L2    S

or

Fig. 7

Содержание 1PAMSH09-SZO-14.5

Страница 1: ...e read this manual carefully and keep it for future reference along with your receipt SINGLE ZONE DUCTLESS MINI SPLIT SYSTEM INSTALLATION MANUAL INDOOR UNIT 1PAMSH09 SZW 14 5 1PAMSH09 SZW 15 1PAMSH12 SZW 15 1PAMSH18 SZW 15 OUTDOOR UNIT 1PAMSH09 SZO 14 5 1PAMSH09 SZO 15 1PAMSH12 SZO 15 1PAMSH18 SZO 15 ...

Страница 2: ... a chart with solutions to the most common problems Referring to this section may save time and prevent the need for a service call in the event of a problem Safety Precautions Installation Precautions 2 Warning 2 Caution 2 Installation Instructions Selecting installation location 3 4 Accessories 4 Indoor unit installation 5 7 Outdoor unit installation 8 9 Air Purging and Test Operation Air Purgin...

Страница 3: ...efective incorrect installation can result in water leakage electrical shock or fire 2 Install the indoor unit per these instructions Make sure it is secured properly to the wall If not installed properly the unit could drop or fall causing injury 3 An independent circuit breaker must be used for each indoor unit If the circuit breaker is not sized properly electrical shock and or a fire can resul...

Страница 4: ...irect sunlight or rain exposure make sure that heat radiation from the condenser is not restricted Do not place animals and plants in the path of the air inlet or outlet Refer to Fig 1 which notes the amount of space there must be between the unit and any walls ceiling fences and other obstacles items Install the outdoor unit on concrete or plastic pad or mount to a wall with the proper brackets s...

Страница 5: ...ping Screw A ST3 9x25 5 8 depends on model 4 Seal for cooling heating models only 1 5 Drain Joint for cooling heating models only 1 6 Connecting pipe assembly Liquid side Φ 1 4 6 35 mm Parts you must purchase The pipe size differs from appliance to appliance Consult the technician for the proper size Φ 3 8 9 52 mm Gas side Φ 3 8 9 52 mm Φ 1 2 12 7 mm Φ 5 8 16 mm 7 Remote control 1 8 Self tapping S...

Страница 6: ... wall with five or eight type A screws NOTE Mount the Installation Plate and drill holes in the wall according to the wall structure and corresponding mounting points on the installation plate The Installation Plate provided with the machine differs based on the model being installed All units are in inches unless otherwise noted Correct orientation of Installation Plate Right rear side refrigeran...

Страница 7: ...nit All wiring must comply with local and national codes and be installed by a certified electrician Suggested Minimum Wire Size AWG American Wire Gauge Appliance Amps AWG Wire Size 10 18 13 16 18 14 25 12 30 10 NOTE The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which is located on the side panel of the unit Please refer to th...

Страница 8: ...staller in case of water leakage Bundle the tubing connecting cable and drain hose with tape securely and evenly as shown in the figures on the right NOTE Because the condensed water from rear of the indoor unit is gathered in the drain pan and is piped out of the room do not put anything else in the drain pan CAUTION Connect the indoor unit first then the outdoor unit Be careful not to let the dr...

Страница 9: ...l drain joint as shown in Figure 14B insert the drain joint into the base pan hole of outdoor unit until it remains fixed with a clicking sound Connecting the drain joint with an extension drain hose purchased locally in case the water drains of the outdoor unit during the heating mode Outdoor Unit Installation Seal Drain joint Base pan hole of outdoor unit A B Fig 14 Fig 13 Strong wind Strong win...

Страница 10: ...ach tube both liquid and gas side tubes between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed Pipe length and refrigerant amount indicated in the chart below Connective pipe length Air purging method Additional amount of refrigerant to be charged Less than 16 4 ft Use vacuum pump More than 16 4 ft Use vacuum pump 9k 12k 18k Liquid side...

Страница 11: ...onnections and outdoor unit connections using a soft brush to check for leakage of the connecting points of the piping If bubbles come out this indicates that the pipes have leakage Leak detector Use the leak detector to check for leakage CAUTION See Figure 20 A Lo packed valve B Hi packed valve C and D are ends of indoor unit connection Test Running Perform test operation after completing gas lea...

Страница 12: ...BUILT TO LAST Distributed by Perfect Aire LLC 5151 Belt Line Rd Suite 878 Dallas TX 75254 Specification and performance data is subject to change without notice Printed in China 877 365 6274 www perfectaire us ...

Отзывы: