1. INTRODUCTION

The  Timesafe  meter  has  been  designed  using  modern  technology  to  give  an  extremely  reliable  unit.  The  modular
construction allows for easy servicing when required. The meter is simple to install and requires no maintenance other
than  regular  emptying  of  the  cash  box.  The  operating  characteristics  as  defined  by  BS-EN60730  are  type  1B.  The
meters comply to the latest EMC and Low Voltage directives, meeting EN60730-1:92, EN50082-1:92, EN55014:93,
and EN60555-2:87.

2. INSTALLATION

The  ADM  Timesafe  meter  is  designed  as  an  independently  surface  mounted
control, and can be corner mounted either left or right. It should not be installed
in locations where the ambient temperature exceeds 40ºC.

Lay the meter on its back and unlock and remove the cash box.

See Figure  1.  Using  a  No.  1,  nine  inch  pozidrive  screwdriver  remove  the
recessed screw and remove the front panel by pulling towards base as far as
possible, lifting bottom edge slightly outwards and then lifting panel upwards.

IMPORTANT. 

It is essential that panel recess is clear of case lip before at-

tempting  to  lift  panel  out.  Rotate  front  panel  and  withdraw  nine  way
connector  from  printed  circuit  board  thus  separating  front  panel  from  the
meter case. Set programming switches (as shown in Section 3) and place
panel in a safe place.

iii.  Position the case on the wall and mark the top centre fixing position. Plug

the wall and fit with No. 8 or 10 screw of not less than 22mm. Hang case
on screw and tighten, use a spirit level to ensure the case is perfectly level.

If the case is not level the coin mechanism may malfunction.

iv.    Mark  the  bottom  two  screw  positions,  remove  case  and  plug  the  holes.

Remove the cable knockouts as required and fix to the wall.

v.  Using a fused double pole switch for the mains input, wire the unit as

 

shown in Figure 2. 

IMPORTANT. 

Use cable of crossectional area not less

 

than 1.0sq. mm and fuse at 5A. The use of 20mm conduit is recommended

 

(use male thread adaptor with lock-ring e.g. Ega type EMA 1ZM).

 

Alternatively fit a 20mm nylon compression cable gland to provide strain relief.

NOTE. 

To  avoid  irreparable  damage  to  the  unit  if  loads  greater  than  4.5A  are  connected  to  the  ADM  Meter  a

non-resettable 5A fuse is fitted. If this fuse is blown it should be replaced by a competent technician or returned to the
factory for replacement.

L

LOAD

OUT

MAINS

IN

EARTH

E

Figure 2

WARNING!

THE EARTH TERMINAL MUST BE CORRECTLY

CONNECTED TO A KNOWN EARTH

ENSURE EARTH WIRE IS ADEQUATELY TRAPPED

BY THE TAGS OF THE CLAMPING WASHERS