VBA-4E4A-G20-ZEJ/M3L-P9

Commissioning

Troubleshooting during configuration

If a fault occurs during the 9-step configuration process, the following table describes the 
behavior of the motor control module.

Fault scenarios

Step

Possible fault

Motor control module reaction

1 ... 6

Incorrect data or parameter values or

steps 1 ... 6 take longer than 10 s

Motor control module remains in normal 
mode.

7 or 8

Incorrect data or parameter values 

The motor control module changes to normal 
operation only when the master sends "0" via 
DO0 ... DO3 and "7" via P0 ... P2.

If "0" or "7" has already been set by the master 
in one of these steps, the motor control module 
switches directly to normal operation. The 
stored ramp is not changed.

Table 5.11

Содержание VBA-4E4A-G20-ZEJ/M3L-P9

Страница 1: ...VBA 4E4A G20 ZEJ M3L P9 AS Interface motor control module Manual...

Страница 2: ...sion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs c...

Страница 3: ...UL Information 7 3 Product Description 8 3 1 Use and application 8 3 2 Housing 8 3 3 Displays and operating elements 9 3 4 Interfaces and connections 11 3 5 Accessories 12 4 Installation 13 4 1 Storag...

Страница 4: ...icable EU type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Target Group Personnel Responsibility...

Страница 5: ...rs or compatible types The motor control module has two inputs for connecting three wire sensors Read through these instructions thoroughly Familiarize yourself with the device before install ing moun...

Страница 6: ...using the device Secure the device against unintended operation To have the device repaired return it to your local Pepperl Fuchs representative or your sales center 1 6 Declaration of Conformity Thi...

Страница 7: ...or indoor use only This device may be operated in altitudes up to 2000 m The ambient temperature range is from 25 C to 70 C The device must be installed in accordance with applicable national laws and...

Страница 8: ...power supply may be loaded in total with 100 mA For each motor a maximum current load of 5 A is permitted briefly 2 s Figure 3 1 VBA 4E4A G20 ZEJ M3L P9 motor control module Essential function and app...

Страница 9: ...Peripheral fault Display of the AS Interface operating states The AUX LED shows the status of the AUX external auxiliary voltage supply 100 120 122 135 5 8 16 6 15 27 5 25 8 54 LED PWR Green LED FAULT...

Страница 10: ...X external auxiliary voltage is inverted Off AUX external auxiliary voltage is missing LED FUSE1 LED FUSE2 Green Status On Power supply for motor is OK Off Power supply for motor is missing Fuse is fa...

Страница 11: ...sensors and motors are connected to the motor control module via cables with round M8 connectors Sensors socket 4 pin Motors socket 5 pin The cable length is 1 m LED DIR Yellow Status On Direction of...

Страница 12: ...pin socket screw locking coding A Suitable counterpart connector M8 4 pin plug screw locking coding A IN1 IN2 1 IN sensor supply 2 Not used 3 IN sensor supply 4 IN input Motor Motor in accordance with...

Страница 13: ...ut the needs for tools The profiled flat cables have a narrow upper side with a visibly offset profile edge and a wide under side profile edge not visible The cable guide allows the flat cables to be...

Страница 14: ...this push the locking bracket 1 slightly to one side 2 Insert the black AUX flat cable with the profile edge 3 to the motor control module into the lower guide see the module tag Black AUX 3 Insert th...

Страница 15: ...at cable The profile edge 2 does not point to the motor control module the flat cable is therefore inserted with reverse polarity The flat cable is located on the reverse polarity protection 1 with a...

Страница 16: ...Connecting motors and sensors Figure 4 4 Connection wiring diagram for motors and sensors n c PWR AUX AUX AS Interface AS Interface FAULT AUX 1 4 3 2 IN 1 2 4 5 3 FUSE IN1 IN2 IN IN IN MOT1 MOT2 MOT...

Страница 17: ...e sets the output data DO0 DO3 to logical 0 Starting Stopping motors DO0 DO1 You can start or stop the motors separately via bits DO0 and DO1 To start motors you must set the corresponding data bit to...

Страница 18: ...This always applies to both motors simultaneously To do this you must parameterize 1 of 4 predefined speed values The speed values correspond to analog voltage values If the master does not change the...

Страница 19: ...nds to the time from stopped to reaching the maximum speed or from the maximum speed to stopped The inclines of the ramps are constant for each of the 8 ramps and independent of the set speed The refe...

Страница 20: ...s are possible as long as a period of 10 s is not exceeded for steps 1 6 The configuration of a new start stop ramp runs in the following phases In steps 1 6 the master sends parameter values to the m...

Страница 21: ...has stored the new start stop ramp and switched back to normal mode Contexts of module communication Note Sequence for command transmission For each step you generally send the data value via DO0 D03...

Страница 22: ...rol module reaction 1 6 Incorrect data or parameter values or steps 1 6 take longer than 10 s Motor control module remains in normal mode 7 or 8 Incorrect data or parameter values The motor control mo...

Страница 23: ...t AUX off AUX external power supply is miss ing Check AUX voltage and AUX flat cable AUX red on AUX external power supply is inverted Correct the polarity of the AUX flat cable in the cable guide AUX...

Страница 24: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 6524A...

Отзывы: