 When used as intended, the AS-Interface safety module allows the operation of sensor-
controlled personal protective equipment up to category 4 and PL e as per ISO 13849 or up to 
SIL 3 as per EN/IEC 61508 and EN/IEC 62061 in combination with an appropriately 
programmed AS-Interface safety monitor. The safety level of the application is determined 
either via a risk analysis, e.g., in accordance with EN 1050, or is taken from a C standard.

2.1.1

Non-secure outputs

2.2

AS-Interface Safety at Work VAA-2E2A-KE1-S/E2 and VAA-2E2A-KE1P-
S/E2

The VAA-2E2A-KE1*-S/E2 is an AS-Interface safety module with two safety-related inputs and 
two outputs. A dual-channel mechanical switch can be connected to the two safety-related 
inputs, or a single-channel mechanical switch can be connected to each input. The outputs are 
conventional electronic outputs that can have a total load of 1 A (max 0.5 A per output). The 
housing is only 22.5 mm wide and 48.5 mm tall and takes up little space in the switch cabinet. 
The module is mounted by snapping it onto the 35 mm DIN rail in compliance with EN 50022. 
An addressing socket is integrated into the module.

The connection is made via plug-in terminals. A four-way (black) terminal block is used for the 
inputs. The AS-Interface is connected via a two-way (yellow) terminal block. Each channel has 
an LED mounted on the top side of the module to display the current switching status. There is 
an LED for monitoring AS-Interface communication and for displaying that the module has the 
address 0.

Warning!

The outputs must not be used for safety-related functions.

Содержание VAA-2E2A-KE1-S/E2

Страница 1: ...SAFETY AT WORK VAA 2E2A KE1 S E2 VAA 2E2A KE1P S E2 Original Operating Instructions FACTORY AUTOMATION MANUAL...

Страница 2: ...very for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recen...

Страница 3: ...E2 and VAA 2E2A KE1P S E2 7 2 3 Peripheral Requirements 8 2 4 Connections and Displays 8 2 5 Interfaces and Connections 9 2 5 1 AS Interface Auxiliary Energy 9 2 5 2 Inputs 10 2 5 3 Outputs 10 3 Commi...

Страница 4: ...2 Category 2 18 6 3 Category 3 18 6 4 Category 4 21 7 Appendix B 24 7 1 Summary of the Requirements for Categories in Accordance with EN 954 1 ISO 13849 1 24 7 2 Certificates 25 7 3 Probability of Fai...

Страница 5: ...laration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Manufacturer 1 3 Target Group Personnel Responsibility for planning assembly commi...

Страница 6: ...es are displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger Thi...

Страница 7: ...puts A dual channel mechanical switch can be connected to the two safety related inputs or a single channel mechanical switch can be connected to each input The outputs are conventional electronic out...

Страница 8: ...AS Interface Transmission system specification version 2 01 dated 05 12 2000 To evaluate a safety related function in accordance with a safety standard all components found in the function must be eva...

Страница 9: ...and VAZ FK S BK for auxiliary energy Designation Description S1 Mechanical switch 1 S1 Mechanical switch 1 S2 Mechanical switch 2 S2 Mechanical switch 2 Designation Description O1 Output 1 O 1 Output...

Страница 10: ...nitoring The inputs are monitored for inter crossed circuits The crossed circuit monitoring function is able to detect low resistance crossed circuits between the two inputs caused by a metallic conne...

Страница 11: ...de 1 X X 0 0 0 0 Outputs independend of inputs X X 1 1 1 1 0 0 0 X X 1 1 Open switch at the input sets the corresponding output 1 1 0 0 0 0 When the switches are closed on the input the master control...

Страница 12: ...Only tested and certified power supplies with safe isolation may be used to supply power These power supplies must have PELV voltage in accordance with EN 50295 IEC 62026 2 and a minimum MTBF of 50 y...

Страница 13: ...a fault message 3 Stop the interruption on the input on the connected mechanical switch or on the cable 4 Enable the input on the safety monitor 3 6 Operating Mode Activating operating modes for the i...

Страница 14: ...30863 2019 04 14 VAA 2E2A KE1 S E2 VAA 2E2A KE1P S E2 Maintenance and Repair 4 Maintenance and Repair 4 1 Maintenance and repair Regular function tests may be necessary depending on the safety categor...

Страница 15: ...lt indication LED red Red communication fault or address is 0 Red flashing output voltage overload PWR LED AS Interface voltage green LED AUX LED Ext auxiliary voltage UAUX green LED IN LED Switching...

Страница 16: ...oof Number type 2 conventional electronic outputs PNP Power supply From external auxiliary voltage UAUX Current 0 5 A per output Voltage UAUX 0 5 V Profile S 7 B IO code 7 ID code B ID1 code F ID2 cod...

Страница 17: ...ional safety EN ISO 13849 1 2015 up to PL e IEC 61508 2010 and IEC 62061 2005 A2 2015 up to SIL 3 Standards NFPA 79 2002 Ambient temperature 25 C 50 C 13 F 122 F Storage temperature 25 C 85 C 13 F 185...

Страница 18: ...plication Connecting two independent mechanical position switches of Category 2 Figure 6 1 6 3 Category 3 The occurrence of a fault must not lead to the loss of the safety function Connection of two d...

Страница 19: ...ss the switches cannot be excluded both channels are needed to achieve a category 3 safety function Figure 6 4 The following function blocks can be parameterized to achieve safety category 3 in this a...

Страница 20: ...f faults must not lead to the loss of the safety function Example 1 Connection of a dual channel mechanical position switch To detect a dangerous accumulation of faults the safety function must be tes...

Страница 21: ...ust be adapted to the application Figure 6 6 The following function blocks can be parameterized to achieve safety category 4 in this application during operation of the AS Interface safety module on a...

Страница 22: ...r their components must be designed constructed selected assembled and combined in accordance with the applicable standards such that they can withstand the expected influences If a fault occurs it ca...

Страница 23: ...tected When an individual fault occurs the safety function is always maintained Some but not all faults are detected An accumulation of undetected faults can lead to the loss of the safety function 4...

Страница 24: ...se of dual channel applications the AS Interface safe input module does not significantly contribute to the PFD or PFH probability of dangerous failure per hour of the overall system The PFD and PFH v...

Страница 25: ...GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Pacif...

Отзывы: