![Pepperl+Fuchs VAA-2E-KE1-S Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/pepperl-fuchs/vaa-2e-ke1-s/vaa-2e-ke1-s_original-instructions-manual_1527685013.webp)
Commissioning
1
8
2
3
1
4
2
0
2
0
-0
9
13
Performing a Function Test
1.
Activate the safety function by interrupting the input. This can be done by actuating a
connected mechanical switch or on the cable.
2.
Check whether the safety monitor detects the interruption without issuing a fault message.
3.
Stop the interruption on the input on the connected mechanical switch or on the cable.
4.
Enable the input on the safety monitor.
4.6
Operating mode
Activating operating modes for the inputs is not possible.
The parameters in the AS interface may influence the performance of the outputs. The chapter
"Operating principle" contains a more accurate description.
4.7
Operation
Programming the safety monitor parameters defines the safety function of the device. Read the
corresponding documentation.
Note
In the case of single-channel safety functions, test the function for each channel.
For applications of category 4/PL e in accordance with ISO 13849-1 or SIL 3 in accordance
with EN/IEC 61508 and EN/IEC 62061, the two inputs must be monitored using the safety
monitor to ensure that they are synchronous.