Synchronization

The sensor is fitted with a synchronization input that suppresses mutual interference from external ultrasonic signals. If this input is not connected,

the sensor operates with internally generated cycle pulses. The sensor can be synchronized by creating external rectangular pulses and by set-

ting the appropriate parameters via the IO-link interface. Each falling pulse edge sends an individual ultrasonic pulse. If the signal at the synchro-

nization input is low for >1 second, the sensor reverts to the normal, unsynchronized operating mode. This also occurs if the synchronization input

is disconnected from external signals (see note below).

If a high signal is applied to the synchronization input for > 1 second, the sensor switches to standby. This is indicated by the green LED. In this

operating mode, the last recorded output statuses are retained. Please observe the software description in the event of external synchronization.

Note:

If the option of synchronizing is not used, the synchronization input must be connected to ground (L-) or the sensor must be operated with a V1-

connection cable (4-pin).

The option of synchronization is not available during the programming process. During synchronization, the sensor can switch to programming

via the IO-link interface. This interrupts the synchronization process and the sensor is no longer synchronized.

The following synchronization modes are available:

1. Multiple sensors (see Technical data for the maximum number) can be synchronized by connecting the synchronization inputs on the sen-

sors. In this case, the sensors synchronize themselves in succession in multiplex mode. Only one sensor sends signals at any one time.

(See note below)

2. Multiple sensors (see Technical data for the maximum number) can be synchronized by connecting the synchronization inputs on the sen-

sors. The sensor interface can be used to parameterize the sensors so that one functions as a master and the others function as slaves.

(See interface description) In this case, the sensors in master/slave mode work simultaneously, i.e. in synchronization where the master sen-

sor plays the role of an intelligent external impulse generator.

3. Multiple sensors can be controlled collectively by an external signal. In this case, the sensors are triggered in parallel and operate synchro-

nously, i.e. at the same time. All sensors must be parameterized via the sensor interface so that they are set to external. See the software

description.

4. Several sensors are controlled with a time delay by an external signal. In this case, only one sensor is externally synchronized at any one

time (see note below). All sensors must be parameterized via the sensor interface so that they are set to external. See the software descrip-

tion.

5. A high signal (L+) or a low signal (L-) at the synchronization input switches the sensor to standby in the case of external parameterization.

Note:

The response time of the sensors increases in proportion to the number of sensors in the synchronization chain. In multiplex mode, the measuring

cycles of the individual sensors run in succession in a chronological sequence.

Note:

The synchronization connection of the sensors supplies an output current in the case of a low signal, and generates an input impedance in the

case of a high signal. Please note that the synchronizing device must have the following driver properties:

Driver current according to L+ > n * high level signal/input impedance (n = number of sensors to be synchronized)

Driver current according to L- > n * output current (n = number of sensors to be synchronized).

LED, 

green

LED L1, yellow

LED L2, yellow

LED, red

In normal mode

Error-free operation

Fault (e.g. compressed air)

On

Off

The output status

retains the last

status

The output status

retains the last

status

Off

On

When programming the trip points or 

trip values

Object detected

No object detected

Confirmation, programming successful

Warning, programming invalid

Off

Off

Flashes 3x

Off

Flashes

Off

Off

Off

Flashes

Off

Off

Off

Off

Flashes

Off

Flashes 3x

When programming the operating 

mode

Programming the output function

Programming the output behavior

Programming the sound cone

Flashes

Off

Off

Off

Flashes

Off

Off

Flashes

Off

Off

Off

Flashes

L1

L2

T1

T2

L1

L2

LED 
green/red

LED yellow

LED yellow