Power Supply PS1000-A6-48.5
Application Notes
20
21
-1
1
37
25.4
Output Circuit Breakers
Standard miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly
used for AC-supply systems and may also be used on 48V branches.
MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics
of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe
regardless of whether the MCB opens or not.
To avoid voltage dips and under-voltage situations in adjacent 48V branches which
are supplied by the same source, a fast (magnetic) tripping of the MCB is desired.
A quick shutdown within 10ms is necessary corresponding roughly to the ride-through time
of PLC's. This requires power supplies with high current reserves and large output capacitors.
Furthermore, the impedance of the faulty branch must be sufficiently small in order
for the current to actually flow. The best current reserve in the power supply does not help
if Ohm’s law does not permit current flow. The following table has typical test results showing
which B- and C-Characteristic MCBs magnetically trip depending on the wire cross section
and wire length.
Figure 25.4 Test circuit
Maximal wire length
1
for a fast (magnetic) tripping:
1
Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length
(+ and – wire).
0.75mm²
1.0mm²
1.5mm²
2.5mm²
C-2A
42m
49m
59m
109m
C-3A
13m
24m
28m
42m