20
21
-1
1
12
Power Supply PS1000-A6-24.5
DC Input
6
DC Input
The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC
source. A supply from the intermediate DC-bus of a frequency converter is not recommended
and can cause a malfunction or damage the unit.
Cpole to L, –pole to N and the PE terminal to an earth wire or to the machine ground.
Figure 6.1
Wiring for DC Input
DC input
Nom. DC 110-150V
±20%
DC input range
Min.
88-180Vdc
Continuous operation
DC input current
Typ.
1.21A
At 110Vdc, at 24V, 5A
Typ.
0.43A
At 300Vdc, at 24V, 5A
Allowed Voltage (+) or (–)
input to Earth
Max. 360Vdc
Continuous according to IEC 60664-1
Turn-on voltage
Typ.
74Vdc
Steady state value
Shut-down voltage
Typ.
67Vdc
Steady state value
+
-
Load
L
PE
+
-
Power Supply
AC
DC
Battery
N