Power Supply PS1000-A6-12.16
Terminals and Wiring
20
21
-1
1
23
16
Terminals and Wiring
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Connecting Terminals
1.
Use appropriate copper cables that are designed for minimum operating temperatures of:
•
60°C for ambient up to 45°C and
•
75°C for ambient up to 60°C minimum
•
90°C for ambient up to 70°C minimum.
2.
Follow national installation codes and installation regulations!
3.
Ensure that all strands of a stranded wire enter the terminal connection!
4.
Unused terminal compartments should be securely tightened.
5.
Ferrules are allowed.
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long
as the average output current through one terminal pin does not exceed 25A. If the current
is higher, use a separate distribution terminal block as shown in Figure 16.2.
Figure 16.1 Daisy chaining of outputs
Input and output
DC-OK-Signal, Shut-down input
Type
Screw terminals
Push-in terminals
Solid wire
Max. 6mm
2
Max. 1.5mm
2
Stranded wire
Max. 4mm
2
Max. 1.5mm
2
American Wire Gauge
AWG 20-10
AWG 24-16
Wire diameter
Max. 2.8mm (including ferrules)
Max. 1.6mm (including ferrules)
Wire stripping length
7mm / 0.28inch
7mm / 0.28inch
Screwdriver
3.5mm slotted or cross-head No 2
3.mm slotted to open the spring
Recommended tightening torque 1Nm, 9lb.in
-
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Maximal 15A continuous for CP5.241-S2
Maximal 25A continuous for all other units
max. 25 A
continuous