Commissioning
Setting the number of readers, operating mode, and addresses
1. Open the hardware catalog and browse through the tree structure until you see the WCS-
PNG210 symbol (PROFINET IO > Additional Field Devices > Gateway > Fuchs
WCS).
2. Click on
+
next to the WCS-PNG210 symbol to expand the tree structure.
3. Select the module with the appropriate number of readers and operating mode and drag it
into the window where the modules are listed.
The selected module is added to the list.
4. To change the input and output address of the module, double-click on the module and
enter the addresses in the
Properties
window.
5. Click on
Transfer
to transfer all the settings to the PLC.
4.5
Data format for modules
In "only Position" operating mode, 4 bytes are reserved for each WCS reader.
Bit
7
6
5
4
3
2
1
0
Byte 0
0
0
0
0
0
P18
P17
P16
Byte 1
P15
P14
P13
P12
P11
P10
P09
P08
Byte 2
P07
P06
P05
P04
P03
P02
P01
P00
Byte 3
0
0
0
DB
ERR
OUT
A1
A0
Table 4.3
Data format for each connected WCS reader in "only Position" operating mode, reader
address = 0...3