Appendix
2
0
1
8
-0
4
43
10.2.3
IO-Link Device Parameters
Note!
The existing indexes for the various sensors differ according to their properties. For example,
indexes for parameterizing an analog output are only available for sensors with an analog
output.
Index
Sub-
index Name
Type
Data
type
Value
Default
Unit
Device Settings
(Data Storage = yes)
0x61
Operation Mode R/W
uint8
0: One Damping
Element (Absolute
Position
Measurement)
1: Two Damping
Elements (Relative
Position
Measurement)
0
Switching Signal Channel 1
(Data Storage = yes)
0x3C
1
Setpoint SP1
R/W
uint16 PMI40: 0 ... 800
PMI80: 0 ... 1600
PMI120: 0 ... 2400
200
400
600
1/20 mm
2
Setpoint SP2
R/W
uint16 PMI40: 0 ... 800
PMI80: 0 ... 1600
PMI120: 0 ... 2400
800
1600
2400
1/20 mm
0x3D
1
Switchpoint
Logic
R/W
uint8
0: Active-High
1: Active-Low
0
2
Switchpoint
Mode
R/W
uint8
0x01
—
Single Point
Mode
0x02
—
Window Mode
0x03
—
Two Point
Mode
0x80
—
Centered
Window Mode
0x80
3
Switchpoint
Hysteresis
R/W
uint16 0: Low
1: Medium
2: High
0
0x40
1
Window Width
R/W
uint16 PMI40: 1 ... 800
PMI80: 1 ... 1600
PMI120: 1 ... 2400
20
1/20 mm
2
Off Delay
R/W
uint16 0 ... 60000
0
ms
3
On Delay
R/W
uint16 0 ... 60000
0
ms
4
Error Behavior
R/W
uint8
0: State Freeze
1: Maximum Position
2: High
3: Low
3
Switching Signal Channel 2
(Data Storage = yes)
0x3E
1
Setpoint SP1
R/W
uint16 PMI40: 0 ... 800
PMI80: 0 ... 1600
PMI120: 0 ... 2400
600
1200
1800
1/20 mm
2
Setpoint SP2
R/W
uint16 PMI40: 0 ... 800
PMI80: 0 ... 1600
PMI120: 0 ... 2400
800
1600
2400
1/20 mm