Direct read/read with trigger signal activated
A read-only tag read takes place either through an appropriate command from the
PLC or through a trigger signal from an attached sensor.
1. Select
Configuration > configure OIT System
.
2. If the window
Invalid parameters...
pops up, close it by clicking on
OK
.
3. Go to the tab
image/check
:
Figure 8.16
Image/testing
tab
4. In order to trigger the read command by PLC, check the box
PLC direct
read
in the image capture area. The OIT system will trigger a read operation
immediately after receiving the command. In order to use the trigger sensor to
read after an appropriate PLC command, deactivate
SPS direct read
. The
OIT system will then trigger a read operation with a rising edge at the trigger
entrance.
5. In order to send the settings to the OIT system, click the button
Write
parameters
in the
OIT system
.
6. In order to close the
parameterization of the OIT system
dialog box, click
on
end
.
Saving a parameter file
It is possible to save the settings in the OIT system parameterization dialog box for
future use. To create a parameter file, proceed as follows:
1. Choose
Configuration > OIT system configuration
.
2. If the
Invalid parameter data...
window opens, close it by clicking
OK
.
The
OIT system parameterization
dialog box opens.
3. Change any settings as necessary.
4. Click
Save file
in the
File system
area.
5. The
Save
dialog box opens.
6. Choose the location where you want the parameter file saved.
7. Confirm by clicking
Save
.
The
Save
dialog box closes.
8. To close the
OIT system parameterization
dialog box, click
Exit
.