Pressure Transmitter LHCR-51, LHCS-51
Commissioning
28
8 1. The hydrostatic pressure for the upper
calibration point is present at the device, here
"300 mbar" (4.5 psi) for example.
2. Select the "Full calib." parameter.
3. Enter the level value, here "3 m" (9.8 ft) for
example. Confirming the value means you
assign the pressure value present to the upper
level value.
Menu path: Setup
→
Extended setup
→
Level
→
Full calib.
9 Result:
The measuring range is set for 0 m to 3 m (9.8 ft).
0 m corresponds to an output current of 4 mA.
3 m (9.8 ft) corresponds to an output current of
20 mA.
Description