Functional Safety KFD2-SR3-(Ex)2.2S

Planning

20

16-03

9

3

Planning

3.1

System Structure

3.1.1

Low Demand Mode of Operation

If there are two control loops, one for the standard operation and another one for 

the functional safety, then usually the demand rate for the safety loop is assumed 

to be less than once per year.

The relevant safety parameters to be verified are:

• the  PFD

avg

 value (average 

P

robability of dangerous 

F

ailure on 

D

emand) and 

the T

1

 value (proof test interval that has a direct impact on the PFD

avg

value)

• the  SFF  value  (

S

afe 

F

ailure 

F

raction)

• the  HFT  architecture  (

H

ardware 

F

ault 

T

olerance)

3.1.2

High Demand or Continuous Mode of Operation

If there is only one safety loop, which combines the standard operation and 

safety-related operation, then usually the demand rate for this safety loop is 

assumed to be higher than once per year.

The relevant safety parameters to be verified are:

• the  PFH  value  (

P

robability of dangerous 

F

ailure per 

H

our)

• Fault reaction time of the safety system 
• the  SFF  value  (

S

afe 

F

ailure 

F

raction)

• the  HFT  architecture  (

H

ardware 

F

ault 

T

olerance)

3.1.3

Safe Failure Fraction

The safe failure fraction describes the ratio of all safe failures and dangerous 

detected failures to the total failure rate.

SFF = (

s

 + 

dd

) / (

s

 + 

dd

 + 

du

)

A safe failure fraction as defined in IEC/EN 61508 is only relevant for elements or 

(sub)systems in a complete safety loop. The device under consideration is 

always part of a safety loop but is not regarded as a complete element or 

subsystem.

For calculating the SIL of a safety loop it is necessary to evaluate the safe failure 

fraction of elements, subsystems and the complete system, but not of a single 

device.

Nevertheless the SFF of the device is given in this document for reference.

Functional Safety KFD2-SR3-(Ex)2.2S

Содержание KFD2-SR3-2.2S

Страница 1: ...Functional Safety Switch Amplifier KFD2 SR3 Ex 2 2S PROCESS AUTOMATION MANUAL ISO9001 2...

Страница 2: ...ivery for Products and Services of the Electrical Industry published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recen...

Страница 3: ...Standards and Directives for Functional Safety 8 3 Planning 9 3 1 System Structure 9 3 2 Assumptions 10 3 3 Safety Function and Safe State 11 3 4 Characteristic Safety Values 12 3 5 Useful Lifetime 1...

Страница 4: ...osal The documentation consists of the following parts Present document Instruction manual Manual Datasheet Additionally the following parts may belong to the documentation if applicable EC type of ex...

Страница 5: ...ons will void any warranty and absolve the manufacturer from any liability The device is developed manufactured and tested according to the relevant safety standards Use the device only for the applic...

Страница 6: ...sequence of actions Danger This symbol indicates an imminent danger Non observance will result in personal injury or death Warning This symbol indicates a possible fault or danger Non observance may c...

Страница 7: ...according to EN 60715 KFD2 SR3 2 2S This signal conditioner provides the galvanic isolation between field circuits and control circuits The device transfers digital signals NAMUR sensors or dry conta...

Страница 8: ...ctives Pepperl Fuchs GmbH Lilienthalstra e 200 68307 Mannheim Germany KFD2 SR3 2 2S KFD2 SR3 Ex2 2S Up to SIL 2 Functional safety IEC EN 61508 part 1 7 edition 2010 Functional safety of electrical ele...

Страница 9: ...this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault reaction time of the safety...

Страница 10: ...equent temperature fluctuations are expected The fault indication output which signals if the field circuits are broken or shorted is not considered in the FMEDA and the calculations The indication of...

Страница 11: ...ety function enable the line fault detection The input loop of all versions is supervised The related safety function is that the outputs go to fault state safe state if a line fault is detected React...

Страница 12: ...or high demand mode HFT 0 SIL SC 2 Safety function Normal inverted operation s 1 145 FIT dd 4 1 FIT du 73 FIT total safety function 1 1 No effect failures and Annunciation failures are not influencin...

Страница 13: ...lures are detected to a huge percentage during the installation and therefore the assumption of a constant failure rate during the useful lifetime is valid However according to IEC EN 61508 2 a useful...

Страница 14: ...tion to ensure the expected output behavior 4 1 Configuration Configuring the Device The device is configured via DIP switches The DIP switches for setting the safety functions are on the front of the...

Страница 15: ...of the plant operator to define the type of proof test and the interval time period Equipment required Digital multimeter with an accuracy of 0 1 Use for the proof test of the intrinsic safety side o...

Страница 16: ...nput The device must detect an external fault This state is indicated by red LED and the relay of the corresponfding output must be de activated 3 Test the outputs with a certain current i e 100 mA an...

Страница 17: ...y loop does not work without the device shut down the application Do not restart the application without taking proper precautions Secure the application against accidental restart 3 Do not repair a d...

Страница 18: ...lculation of SFF not part Probability of failure of components that are not in the safety loop total safety function Safety function HFT Hardware Fault Tolerance MTBF Mean Time Between Failures MTTR M...

Страница 19: ...Functional Safety KFD2 SR3 Ex 2 2S Notes 2016 03 19 Pulscon LTC50 HART...

Страница 20: ...rl fuchs com PROCESS AUTOMATION PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs represe...

Отзывы: