Dat
e
of
iss
u
e
1
1
/30/
07
805639
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Display modes and error messages
14
6
Display modes and error messages
The following appear on the display in normal mode:
•
the current values for HART variables PV, SV, TV, QV in the selected unit and
•
the actual current output values Ch1, Ch2, Ch3 in mA.
•
Please use the
S
and
T
keys to select the displayed measured value
or current output value.
•
To select the units for the measured values see section 8.2.
•
The display is updated every time the HLC receives a HART command 3 message from the field
device.
•
Current output values are displayed as a four-digit number. The decimal point is set to give the best
possible resolution.
•
The floating decimal values for the HART variables are displayed as follows:
−
if possible as a four-digit number with decimal point and without an exponent (negative values
have three digits because of minus sign)
−
a number may be rounded up (0.3456 appears as 0.346)
−
if this display is not possible, the mantissa and exponent are displayed alternately.
If the restart inhibit (see section 8.5.5 and 8.5.7) is triggered but the device continues operating
normally, a corresponding message appears in the second line of the display.
If a fault occurs, one of the following messages is displayed until the fault is rectified:
•
Err device fault
(red LED lights up)
•
Err communication error
(red LED flashes)
•
Err
sensor fault
(red LED flashes)
If switching the HLC on/off and checking the cables does not rectify the fault, please contact
Fuchs or the field device manufacturer.
The relays power down when a fault occurs.
For information on the behaviour of the current output in the event of a fault, see section 8.4.4.
Содержание KFD2-HLC-1.D
Страница 1: ...HANDBUCH PROZESSAUTOMATION PROCESS AUTOMATION MANUAL HART LOOP CONVERTER KFD2 HLC EX 1 D ISO9001 ...
Страница 40: ...Date of issue 11 30 07 805639 HART Loop Converter KFD2 HLC Ex 1 D Notes 38 ...
Страница 41: ...Date of issue 11 30 07 805639 39 HART Loop Converter KFD2 HLC Ex 1 D Notes ...
Страница 42: ...Date of issue 11 30 07 805639 HART Loop Converter KFD2 HLC Ex 1 D Notes 40 ...