Functional Safety KFD2-CD-(Ex)1.32-**

Planning

201

8-11

9

3

Planning

3.1

System Structure

3.1.1

Low Demand Mode of Operation

If there are two control loops, one for the standard operation and another one for the 

functional safety, then usually the demand rate for the safety loop is assumed to be less 

than once per year.

The relevant safety parameters to be verified are:

the  PFD

avg

 value (average 

P

robability of dangerous 

F

ailure on 

D

emand) and 

the T

1

value (proof test interval that has a direct impact on the PFD

avg

value)

the SFF value (

S

afe 

F

ailure 

F

raction)

the HFT architecture (

H

ardware 

F

ault 

T

olerance)

3.1.2

High Demand or Continuous Mode of Operation

If there is only one safety loop, which combines the standard operation and safety-related 

operation, then usually the demand rate for this safety loop is assumed to be higher 

than once per year.

The relevant safety parameters to be verified are:

the  PFH  value  (

P

robability of dangerous 

F

ailure per 

H

our)

Fault reaction time of the safety system 

the SFF value (

S

afe 

F

ailure 

F

raction)

the HFT architecture (

H

ardware 

F

ault 

T

olerance)

3.1.3

Safe Failure Fraction

The safe failure fraction describes the ratio of all safe failures and dangerous detected failures 

to the total failure rate.

SFF = (

s

 + 

dd

) / (

s

 + 

dd

 + 

du

)

A safe failure fraction as defined in IEC/EN 61508 is only relevant for elements or (sub)systems 

in a complete safety loop. The device under consideration is always part of a safety loop but is 

not regarded as a complete element or subsystem.

For calculating the SIL of a safety loop it is necessary to evaluate the safe failure fraction of 

elements, subsystems and the complete system, but not of a single device.

Nevertheless the SFF of the device is given in this document for reference.

Содержание KFD2-CD-1.32 Series

Страница 1: ...ISO9001 2 Functional Safety Current Voltage Driver KFD2 CD Ex 1 32 PROCESS AUTOMATION MANUAL...

Страница 2: ...livery for Products and Services of the Electrical Industry published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most rece...

Страница 3: ...ces 7 2 3 Marking 8 2 4 Standards and Directives for Functional Safety 8 3 Planning 9 3 1 System Structure 9 3 2 Assumptions 10 3 3 Safety Function and Safe State 11 3 4 Characteristic Safety Values 1...

Страница 4: ...ting Dismounting Disposal The documentation consists of the following parts Present document Instruction manual Manual Datasheet Additionally the following parts may belong to the documentation if app...

Страница 5: ...nd understood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty and abso...

Страница 6: ...e displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This sym...

Страница 7: ...ety applications The device supplies 2 wire transmitters The device transfers a voltage or a current signal from the non hazardous area to I P converters electrical valves and positioners located in t...

Страница 8: ...erl fuchs com KFD2 CD 1 32 KFD2 CD Ex1 32 0 KFD2 CD Ex1 32 1 KFD2 CD Ex1 32 3 KFD2 CD Ex1 32 6 KFD2 CD Ex1 32 10 KFD2 CD Ex1 32 12 KFD2 CD Ex1 32 13 KFD2 CD Ex1 32 15 KFD2 CD Ex1 32 21 Up to SIL 2 Fun...

Страница 9: ...e demand rate for this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault reaction t...

Страница 10: ...subtracted from the dangerous undetected failure rate du and regarded in a different way If a reaction is introduced that brings the application to the safe state then the failure rate fail high can...

Страница 11: ...on the device version Reaction Time The reaction time for all safety functions is 50 ms Device Input signal Output signal KFD2 CD 1 32 KFD2 CD Ex1 32 0 0 mA to 20 mA 0 mA to 20 mA KFD2 CD Ex1 32 1 4 m...

Страница 12: ...h a deviation of less than 2 voltage driver function HFT 0 SIL hardware 2 sd su 1 1 No effect failures and No part failures are not influencing the safety function and are therefore not included in th...

Страница 13: ...components that have this constant domain and that the validity of the calculation is limited to the useful lifetime of each component It is assumed that early failures are detected to a huge percenta...

Страница 14: ...at are suitable for this safety application 5 Check the safety function to ensure the expected output behavior 4 1 Installation Connecting the Field Device Connect the field device to the current volt...

Страница 15: ...accordance with the characteristic safety values See chapter 3 4 It is under the responsibility of the plant operator to define the type of proof test and the interval time period Equipment required D...

Страница 16: ...er the test Figure 5 1 Proof test set up for KFD2 CD Ex1 32 Usage in Zone 0 1 2 Div 1 2 only for KFD2 CD Ex1 32 Step No Input value Output value Current source mA Voltage source V Current sink mA Volt...

Страница 17: ...s not work Take appropriate measures to protect personnel and equipment while the safety function is not available Secure the application against accidental restart 3 Do not repair a defective device...

Страница 18: ...sed for calculation of SFF not part Probability of failure of components that are not in the safety loop total safety function Probability of failure of components that are in the safety loop HFT Hard...

Страница 19: ...Functional Safety KFD2 CD Ex 1 32 Notes 2018 11 19...

Страница 20: ...rl fuchs com Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check www pepperl fu...

Отзывы: