2
018-
11
14
Functional Safety KFD2-CD-(Ex)1.32-**
Mounting and Installation
4
Mounting and Installation
Mounting and Installing the Device
1. Observe the safety instructions in the instruction manual.
2. Observe the information in the manual.
3. Observe the requirements for the safety loop.
4. Connect the device only to devices that are suitable for this safety application.
5. Check the safety function to ensure the expected output behavior.
4.1
Installation
Connecting the Field Device
Connect the field device to the current/voltage driver.
If possible, use a field device that detects values that are too high and reacts
on them accordingly. For field devices with current output, this value is > 21 mA.
For field devices with voltage output, this value is > 5.25 V or > 10.5 V.
4.2
Configuration
A configuration of the device is not necessary and not possible.