Commands
20
13
-0
3
27
If a R/W head is not connected, the following second response appears.
60031000#<CR>.
Get state (GS)
The command
GS
retrieves the settings.
Command:
GS#<CR>
Response:
<Status>0<Command code>0<Data length>TO:<Timeout> BD:<Baud rate>
HD1:<Status><Tag type>#<CR>
Example of a response:
00950016 TO:0 BD:38400 HD1:022#<CR>
As well as these commands, you can use any commands that are defined for the
IDENTControl with serial interface. A description of the commands is included in
the manual for the IDENTControl with serial interface (e.g. IC-KP2-1HRX-2V1
manual).
7.1.2
Legend
Note!
The responses from the IDENTControl Compact with an interface for PROFIBUS
DP are different from the responses of the IDENTControl with a serial interface.
PROFIBUS device: <Status>0<Command code><Channel><Data length> ...
Device with serial interface: <Status><Channel> ...
Example: Set data carrier type 33 for read head channel 1 using the "Change tag"
(CT) command:
Command:
CT133#<CR>
Response:
00041000#<CR>
(status=0, command code=04, read head channel=1)
<Command code>
:
Two-digit hexadecimal code, same as the command code
transferred via the PROFIBUS
<Channel>
:
Reading head channel (channel 1)
<Data length>
:
Three-digit hexadecimal code, number of other digits
included in the response (excluding end identifier)