Installation
20
13-
02
17
Connecting the R/W head
Connect the R/W head with compatible connecting cable to the socket on the top
of the enclosure via the M12 connector.
Compatible connecting cables see chapter 4.2.1.
5.4.3
Ground connection
Connect the IDENTControl Compact unit to ground via a screw on the right under
the housing.
Connecting the IDENTControl Compact to ground
Screw the ground conductor to the housing with a crimp connector.
5.4.4
PROFIBUS connection guide
The data lines RxD/TxD-P and RxD/TxD-N are also referred to as A and B lines.
There are no PROFIBUS specifications that indicate which color wire on the data
cable should be attached to which terminal. The wire color must be unified within
the entire plant. If you use a transfer cable with red and green wires, we
recommend the following assignment:
Use the B-coded M12 socket and Y Cable ICZ-3T-0,3M-PUR ABG-V15B-G to
connect the IDENTControl Compact unit to the PROFIBUS DP.
Note!
In order to guarantee safe grounding, mount the serrated washer between the
crimp connector and the housing.
Use a ground conductor lead with a cross-section of at least 4 mm
2
.
1
Housing
2
Serrated lock washer
3
Crimp connector
4
Lock screw
1
2
4
3
RxD/TxD-N (A line):
green
RxD/TxD-P (B line):
red