Appendix A
2014-
02
111
Output instance 104d - 32 bytes
Input instance 154d - 32 bytes
Additionally, the IDENTControl requires 32 bytes of input data and sends back 32 bytes of
output data as a result.
Setting tag type IPC03 on channels 1 and 2
Send a Change tagcommand as an implicit command:
Bytes
Class, instance, attribute
Description
0 - 7
64h, 01d, 01h
Channel 1 [8]
8 - 15
64h, 02d, 01h
Channel 2 [8]
16 - 23
64h, 03d, 01h
Channel 3 [8]
24 - 31
64h, 04d, 01h
Channel 4 [8]
Bytes
Class, instance, attribute
Description
0 - 7
65h, 01d, 01h
Channel 1 [8]
8 - 15
65h, 02d, 01h
Channel 2 [8]
16 - 23
65h, 03d, 01h
Channel 3 [8]
24 - 31
65h, 04d, 01h
Channel 4 [8]
Note!
The input and output instances can be configured via the display. However, setting should be
performed via the program while the plant is operating to permit easier replacement or
extension to the plant.
Ele-
ment
Implicit
telegram
Use
Contents Description
1
Byte 0 Command code
04h
Command
CT
(Change tag)
Byte 1 Channel/Toggle bit
00h
The element defined the
channel.
Toggle bit = 0
Byte 2 Tag type (high byte)
30h
IPC 03
Byte 3 Tag type (low byte)
33h
IPC 03
Byte 4
00h
Not used
Byte 5
00h
Not used
Byte 6
00h
Not used
Byte 7
00h
Not used
2
Byte 8 Command code
04h
Command
CT
(Change tag)
Byte 9 Channel/Toggle bit
00h
The element defined the
channel.
Toggle bit = 0
Byte 10 Tag type (high byte)
30h
IPC 03
Byte 11 Tag type (low byte)
33h
IPC 03
byte 12
00h
Not used
Byte 13
00h
Not used
Byte 14
00h
Not used
Byte 15
00h
Not used