Functional Safety HiD282*, HiD284*

Operation

Proof Test Procedure

1.

Put out of service the entire safety loop. Protect the application by means of other measures.

2.

Prepare a test set-up, see figures below.

3.

Simulate the sensor state by connecting a potentiometer, a resistor for short circuit detection 

or by a resistor for lead breakage detection.

Test each input channel individually.

4.

Connect a potentiometer of 4.7 k

 (threshold for normal operation) to the input.

 The threshold must be between 1.4 mA and 1.9 mA, the hysteresis must 

be between 170

µ

A and 250

µ

A.

• If the input current is above the threshold the relay must be activated for normal mode 

of operation. The yellow LED lights up.

• If the input current is below the threshold the relay must be activated for inverted mode 

of operation. The yellow LED lights up.

5.

Connect a resistor R

SC

 (220

) or a resistor R

LB

 (150 k

) to the input.

 The device must detect an external fault. This state is indicated by red LED and the relay 

of the corresponding output must be de-activated. The yellow LED is off.

6.

For HiD282* devices

Connect a load of 240 

/2.5 W to the output.

For HiD284* devices

Connect a load of 2.4 k

 to the output.

7.

For HiD282* devices

Test all relay outputs with a specific current, e. g. 100 mA. To avoid electric shock, 

use a test voltage of 24 V DC. Check that the relay contacts are open.

 The relays must be de-activated. The relay contacts must 

definitely open

.

For HiD284* devices

Test all transistor outputs with a specific current, e. g. 10 mA. To avoid electric shock, 

use a test voltage of 24 V DC. Check that the transistors are not conducting.

 The transistors must be de-activated. The transistor outputs must 

definitely not 

conducting

.

8.

After the test, reset the device to the original settings.

9.

Check the correct behavior of the safety loop. Is the configuration correct?

10.

Secure the DIP switches to prevent unintentional adjustments.

Содержание HiD2842

Страница 1: ...ISO9001 2 Functional Safety Switch Amplifier HiD282 HiD284 Manual...

Страница 2: ...ion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs co...

Страница 3: ...Function 8 2 3 Interfaces 8 2 4 Marking 9 2 5 Standards and Directives for Functional Safe 9 3 Planning 10 3 1 System Structure 10 3 2 Assumptions 11 3 3 Safety Function and Safe State 12 3 4 Characte...

Страница 4: ...Functional Safety HiD282 HiD284 Contents 4 2021 10...

Страница 5: ...ing Dismounting Disposal The documentation consists of the following parts Present document Instruction manual Manual Datasheet Additionally the following parts may belong to the documentation if appl...

Страница 6: ...d understood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty and absol...

Страница 7: ...displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symb...

Страница 8: ...ault A separate fault indication output is available HiD284 The HiD2842 device is a 2 channel isolated barrier The HiD2844 device is a 4 channel isolated barrier This isolated barrier is used for intr...

Страница 9: ...fuchs com HiD2822 HiD2824 HiD2842 HiD2844 Up to SIL 2 Note If you design the safety loops in homogeneous redundancy HFT 1 you can use the devices in applications up to SIL 3 Functional safety IEC EN 6...

Страница 10: ...ually the demand rate for this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault re...

Страница 11: ...f 2 5 based on experience A similar factor must be used if frequent temperature fluctuations are expected Do not use more than one input channel of a multi channel device for a safety loop as the chan...

Страница 12: ...sheet the input loops of all device versions are supervised The related safety function is defined as the outputs are de energized safe state if there is a line fault detected Reaction Time The fault...

Страница 13: ...the safety function 156 FIT 162 FIT no part 34 FIT 34 FIT SFF 1 72 2 88 4 MTBF 2 2 acc to SN29500 This value includes failures which are not part of the safety function MTTR 24 h The value is calcula...

Страница 14: ...influencing the safety function and are therefore not included in SFF and in the failure rates of the safety function 127 FIT 125 FIT no part 34 FIT 34 FIT SFF 1 75 3 86 6 MTBF 2 2 acc to SN29500 Thi...

Страница 15: ...at the useful lifetime can be reduced if the device is exposed to the following conditions highly stressful environmental conditions such as constantly high temperatures temperature cycles with high t...

Страница 16: ...Check the safety function to ensure the expected output behavior 4 1 Configuration Configuring the Device The device is configured via DIP switches The DIP switches for setting the safety functions a...

Страница 17: ...es See chapter 3 4 It is under the responsibility of the plant operator to define the type of proof test and the interval time period Check the settings after the configuration by suitable tests 5 1 1...

Страница 18: ...SC 220 or a resistor RLB 150 k to the input The device must detect an external fault This state is indicated by red LED and the relay of the corresponding output must be de activated The yellow LED is...

Страница 19: ...hat repeats one NAMUR input Test all inputs outputs and safety loops that are used in the safety application HiD2822 Zone 0 1 2 Div 1 2 Zone 2 Div 2 Termination Board Multimeter mA Multimeter mA RLB R...

Страница 20: ...input HiD2822 Zone 0 1 2 Div 1 2 Zone 2 Div 2 Termination Board Multimeter mA Multimeter mA RLB RSC 240 2 5 W 24 V DC Multimeter mA 240 2 5 W 24 V DC SL2 SL1 8a 7a 8b 7b 10a 9a 9b 10b 11 14 17 18 12 1...

Страница 21: ...not work Take appropriate measures to protect personnel and equipment while the safety function is not available Secure the application against accidental restart 3 Do not repair a defective device A...

Страница 22: ...afety function Probability of failure of components that are in the safety loop HFT Hardware Fault Tolerance MTBF Mean Time Between Failures MTTFD Mean Time To dangerous Failure MTTR Mean Time To Rest...

Страница 23: ...Functional Safety HiD282 HiD284 Notes 2021 10 23...

Страница 24: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 7253A...

Отзывы: