2.4
Characteristic Safety Values
HiD2025, HiD2026
Parameters acc. to IEC 61508
Values
Assessment type
FMEDA report
Device type
A
Demand mode
Low Demand Mode or High Demand Mode
Safety function
2
Transfer of analog values
HFT
0
SIL
2
s
1
216 FIT
dd
0 FIT
du
92 FIT
no effect
2
112 FIT
not part
7.1 FIT
total (safety function)
308 FIT
SFF
70 %
MTBF
3
362 years
PFH
9.2 x 10
-8
1/h
PFD
avg
for T
proof
= 1 year
4.04 x 10
-4
PFD
avg
for T
proof
= 2 years
8.07 x 10
-4
PFD
avg
for T
proof
= 5 years
2.02 x 10
-3
1
"Not considered" failures are considered 50 % as dangerous undetected failures
du
and 50 % as safe
detected failures.
2
"No effect" failures are not influencing the safety functions and are therefore added to the
s
.
3
acc. to SN29500. This value includes failures which are not part of the safety function.
Table 2.2