![Pepperl+Fuchs HiD2025 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/pepperl-fuchs/hid2025/hid2025_manual_1527908014.webp)
2
014-
05
14
Safety Manual SIL HiD202*(SK), HiD2030(SK)
Proof Test
4
Proof Test
4.1
Proof Test Procedure
According to IEC 61508-2 a recurring proof test shall be undertaken to reveal
potentially dangerous failures that are otherwise not detected by diagnostic tests.
The functionality of the subsystem must be verified at periodic intervals
depending on the applied PFD
avg
in accordance with the data provided in this
manual. see chapter 2.4.
It is under the responsibility of the operator to select the proof test and regard the
defined interval time period.
With the following instructions a proof test can be performed which will reveal
almost all of the possible dangerous faults (diagnostic coverage > 99 %).
The ancillary equipment required:
• Digital multimeter with an accuracy better than 0.1 %
For the proof test of the intrinsic safety side of the devices, a special
digital multimeter for intrinsically safe circuits must be used.
Intrinsically safe circuits that were operated with non-intrinsically
safe circuits may not be used as intrinsically safe circuits
afterwards.
• Power supply set at nominal voltage of 24 V DC
• For SK versions: Power supply 24 V DC and lead resistor 250
/1 W
• Process calibrator with mA current source/sink feature (accuracy better
than 20
µ
A)
The entire measuring loop must be put out of service and the process held in
safe condition by means of other measures.
Prepare a test set-up for testing the devices (view Figures). Choose the
proper input terminals (passive input or active input) in accordance with the
specific application and follow the steps indicated in the table below.
Restore the safety loop. Any by-pass of the safety function must be removed.
Proof Test for all Channels
Step No.
Set input value (mA) Measurement point
Output value (mA)
Output value (V)
1
20.0
20.0
±
0.4
5.0
±
0.1
2
12.0
12.0
±
0.4
3.0
±
0.1
3
4.0
4.0
±
0.4
1.0
±
0.1
4
23.0
23.0
±
0.4
5.75
±
0.1
5
0
< 0.2
< 0.05
Table 4.1
Safety Manual SIL HiD202*(SK), HiD2030(SK)