Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)
Operation
20
21
-1
0
17
Proof Test Procedure
1.
Disconnect the field circuit.
2.
Check the device as shown in the following tables.
3.
After check reset the device to the necessary settings.
4.
Connect the field circuit again.
5.
Check the correct behavior of the safety loop. Is the configuration correct?
Test No.
Input or Test Input
Output (mA)
1
V
Test 1
= 24 V DC
between terminals 10+ and 9-
•
ETS output (terminals 2, 3): shows < 10
•
LED TST is flashing
2
V
Test 2
= 24 V DC
between terminals 11+ and 9-
•
ETS output (terminals 2, 3): shows < 10
•
LED TST is flashing
3
V
Test 3
= 24 V DC
between terminals 12+ and 9-
•
ETS output (terminals 2, 3): shows < 10
•
LED TST is flashing
4
V
Test
= 24 V DC
between terminals 10+, 11+, 12+ and 9-
•
ETS output (terminals 2, 3): shows < 10
•
LED TST is flashing
5
V
Test
= 0 V DC
between terminals 10+, 11+, 12+ and 9-
•
ETS output (terminals 2, 3): OL (overload)
•
LED TST is off
6
V
input
= 24 V DC
between terminals 7+ and 8- with regular input
polarity
between terminals 7- and 8+ with inverted input
polarity
•
ETS output (terminals 2, 3): shows < 10
•
LED OUT is on
Table 5.1 Expected test results for the proof test of KFD0-RSH-1.1E.1