Characteristic Safety Values
SIL 2 Versions: HiC2027(DE), KCD2-STC-(Ex)1.2O(.DE)
Parameters acc. to IEC 61508
Characteristic values
Assessment type and documentation
Full assessment
Device type
A
Operating mode
Low Demand Mode or High Demand Mode
HFT
0
SIL (SC)
2
Safety function
Transfer of analog signals
s
1
1
"No effect failures" and "Annunciation failures" are not influencing the safety function and are therefore not
included in SFF and in the failure rates of the safety function.
0 FIT
dd
222 FIT
du
55 FIT
annunciation
0 FIT
total (safety function)
277 FIT
total (one channel)
920 FIT
SFF
1
80 %
PTC
100 %
MTBF
2
2
acc. to SN29500. This value includes failures which are not part of the safety function/MTTR = 24 h. The
value is valid for one channel only.
124 years
PFH
5.49 x 10
-8
1/h
PFD
avg
for T
1
= 1 year
2.40 x 10
-4
PFD
avg
for T
1
= 2 years
4.81 x 10
-4
PFD
avg
for T
1
= 5 years
1.20 x 10
-3
Reaction time
< 50 ms
Table 3.8