2
016-
10
58
PROFIBUS Power Hub Segment Coupler 3 (SK3)
Parameter Reference List
PA Segment Diagnostic Parameters
Redundancy Partner Parameters
16
Segment maintenance required:
0: False
1: True
17
Segment out of specification:
0: False
1: True
Bit
Description
0
Live list status:
0: OK
1: No PA slave detected in segment live list
1
Watchdog status:
0: OK
1: DP watchdog time too short
2
Device address status:
0: OK
1: Double slave address (other device or BIS)
3
Reserved
4
Master diagnostic status:
0: OK
1: PA master not in token ring
5
Hardware state:
0: OK 1:
Segment MAU error
6
Segment maintenance required
0: False
1: True
7
Segment out of specification
0: False
1: True
Name
Description
Software version (R)
Software version of the redundancy partner.
Serial number (R)
Serial number of the redundancy partner.
Static revision (R)
Static revision counter of the redundancy partner.
Redundancy diagnostics
Diagnostic status of the redundancy partner.
Redundancy information
Redundancy information of the redundancy partner.
Bit
Description