PROFIBUS Power Hub Segment Coupler 3 (SK3)
Advanced Diagnostics with the PROFIBUS Power Hub
Figure 7.2
Topology of diagnostic connection via diagnostic bus
Hardware
Description
Segment 1...4
PROFIBUS PA segments
HD2-DM-A
Advanced diagnostic module (ADM) on fieldbus Power Hub
motherboard.
HD2-GTR-4PA
Gateway module on gateway motherboard.
Diagnostic Server
Server or Cabinet PC on which the FieldConnex
®
Diagnostic
Server (FDS) is running. The Server is connected to the
advanced diagnostic module via the RS-485 diagnostic bus.
Firmware / Hardware
Description
Operator application
Application on which the plant management or operator
system is running. An OPC-DA client can also be running
here.
Maintenance application
Host application for the FDT frame.
Converter
Device which provides the connection between serial Ethernet
and RS–485. Since the FDS works on a serial COM port, a
converter is needed to connect the FDS with the RS–485
diagnostic bus in the cabinet.
HD2-DM-E
Segment 1
Segment 2
Segment 4
Segment 1
Segment 2
Segment 3
Segment 4
Diagnostic Server
FDS
TCP/IP
Power Hub
Motherboard
Operator Application
Asset
Management
Diagnostic Bus
RS-485
OPC-DA
Con
v
e
rt
er
HD2-DM-A
Serial Com Port
HD2-DM-E
Gateway
Motherboard
HD2-GTR-4PA
Maintenance Application
FDT Frame
DTM
Diagnostic Manager
PROFIBUS DP