Pepperl+Fuchs F2D0-TI-Ex8.FF Series Скачать руководство пользователя страница 6

 2

017-

05

6

Temperature Multi-Input Device

Introduction

Warning Messages

You will find warning messages, whenever dangers may arise from your actions. It is mandatory 

that you observe these warning messages for your personal safety and in order to avoid 

property damage.
Depending on the risk level, the warning messages are displayed in descending order as 

follows:

Informative Symbols

Action

This symbol indicates a paragraph with instructions. You are prompted to perform an action or 

a sequence of actions.

Danger!

This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.

Warning!

This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.

Caution!

This symbol indicates a possible fault.
Non-observance could interrupt the device and any connected systems and plants, or result in 

their complete failure.

Note!

This symbol brings important information to your attention.

Содержание F2D0-TI-Ex8.FF Series

Страница 1: ...Temperature Multi Input Device F2D0 TI Ex8 FF RD0 TI Ex8 FF 6 2 0 DEV_REV 02 PROCESS AUTOMATION MANUAL...

Страница 2: ...elivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most re...

Страница 3: ...allation 14 3 2 1 TM I Cable and Connection Information 14 3 2 2 F2 Housing Degree of Protection 15 3 2 3 Grounding and Shielding 18 3 2 4 Electrical Connection 19 3 2 5 Fieldbus and Shield Connection...

Страница 4: ...0 6 3 Sensor Block 31 6 4 Concentrator Block 32 6 5 AI Function Block 33 6 6 MAI Function Block Errors 33 6 7 Diagnostic Summary 34 6 8 Recommended Action for Field Diagnostics according to NE 107 35...

Страница 5: ...station of conformity Certificates Control drawings Additional documents 1 2 Target Group Personnel Responsibility for planning assembly commissioning operation maintenance and dismounting lies with t...

Страница 6: ...s Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indicates an imminent danger Non observance will result i...

Страница 7: ...device may be operated in Zone 1 For applications in Zone 1 the type of protection must be Ex i The device may be installed in Zone 2 For Zone 2 applications the type of protection must be Ex nA or E...

Страница 8: ...can result in a current voltage flashover generating sparks The sparks can ignite the surrounding potentially explosive atmosphere Ensure you observe IEC EN 60079 14 and IEC EN 60079 25 for the verifi...

Страница 9: ...g point for connecting the temperature multi Input device to earth with M4 screw 3 Cable gland for the fieldbus IN cable For outside dimensions see datasheet 4 8 cables glands for inputs wrench size A...

Страница 10: ...on 4 Status LED for power 5 Dip switches for configuration 6 Separation wall Used if the temperature multi input device is supplied by a non intrinsical ly safe fieldbus 7 DIN mounting rail 8 Mounting...

Страница 11: ...ing RD0 TI Ex8 RD0 TI Ex8 is designed for mounting on a 35 mm DIN rail in accordance with EN 50022 Danger Danger to life from using damaged or repaired devices Using a defective or repaired device can...

Страница 12: ...mount the device Take off the device in reverse order RD0 TI Ex8 Installations Depending on the application the RD0 TI Ex8 must be mounted in a suitable environment If mounted in Zone 2 for an Ex nA a...

Страница 13: ...ween intrinsically safe and non intrinsically safe signals Danger Explosion hazard from inadequate or missing separation appliance If you fail to apply the required separation appliance e g a separati...

Страница 14: ...tion interface Service interface see image on page 10 Only trained specialists authorized by Pepperl Fuchs may carry out parameterization tasks via the Service interface Danger Explosion hazard from i...

Страница 15: ...nst mechanical hazard The following table with tightening torques offers an approximate guideline F2D0 TI Ex8 Tightening Torques for Cap Nuts and Counterparts Danger Explosion hazard or danger to life...

Страница 16: ...as shown 1 Seal 1 used in the following instance Type M20 x 1 5 Terminal area 5 8 mm 2 Seal 2 obligatory 3 Move the required seal s over the cable until after the last seal about 5 mm insulation protr...

Страница 17: ...the cap nut from the temperature multi input device 3 Remove the inner plastic piece and slip it onto the cable move it far enough over the cable so it completely surrounds the cable insulation Ensur...

Страница 18: ...ng the housing cover Visually inspect the housing for any visible signs of damage on the cover seal If damaged replace the seal with an original seal wear part Tightening torque for the screws of the...

Страница 19: ...The grounding connection must be secured against loosening and corrosion e g by using tinned cable plates Shielding the R Electronic Component in Intrinsically Safe Segments The shield terminal S of...

Страница 20: ...he sensor input that is transferred from the transducer block to the function block independent of the hardware input of an input channel For safety reasons it is recommended to set the switch to OFF...

Страница 21: ...erature of the TM I device Information on EMC filter settings Simultaneous output of values and diagnostics information of all channels Analog Input AI Blocks The analog input AI blocks conform to the...

Страница 22: ...ty of the measurement value For more information see chapter 5 Figure 4 1 Function block interaction Number Selected sensor Usable by 1 Sensor 1 AI 2 Sensor 2 AI 3 Sensor 3 AI 4 Sensor 4 AI 5 Sensor 5...

Страница 23: ...ng tool you use For offline parameterization a capability file is available Unless the manufacturer of the control system has imported the files already you find them on the Internet on the Pepperl Fu...

Страница 24: ...ignored It will not produce a configuration error if it is set to another value than 2 wire Measurement Unit You can select between several units for Primary Value Value via the Sensor Range Units In...

Страница 25: ...y be necessary to turn off sensor diagnostics if the device is connected to a calibration source that interferes with the sensor monitoring 2 Write Execute user calibration to Calibration Mode paramet...

Страница 26: ...ut of service and AUTO In OOS mode measurement is disabled and the sensor can be configured and or calibrated In AUTO mode measurement is enabled all functional parameters except Sensor Diagnostics ar...

Страница 27: ...configured In AUTO mode body temperature status is GOOD Note that the concentrator block mode does not affect write protection of the sensor parameters since they solely depend on the target block mo...

Страница 28: ...monitors its internal hardware and body temperature If an error occurs the following happens The status of all primary values switches to BAD The resource block BLOCK_ERR error parameter sets the bit...

Страница 29: ...dications LED Status and Error Indication 1 2 3 LED Statuses Cause Remedy PWR green OFF No power supply Check power supply Check fieldbus cable wiring Permanentl y ON Power available COM red OFF Commu...

Страница 30: ...meterization If this error occurs repeatedly send the device to Pepperl Fuchs for repair Device needs maintenance now Hardware error Send device to Pepperl Fuchs for repair Simulate active Simulation...

Страница 31: ...oblems below OOS The target mode of the block is OOS Set block to Auto mode Transducer Error XD_ERROR Configuration error See above at BLOCK_ERR See above at BLOCK_ERR I O failure The sensor value exc...

Страница 32: ...IP switch to OFF See chapter 3 2 6 Block is in AUTO mode Set MODE_BLK Target to OOS Table 6 3 Common sensor block problems Problem Remedy Parameter Message Cause Procedure BLOCK_ERR Body temperature o...

Страница 33: ...block errors Problem Remedy Cause Procedure Function block does not leave OOS mode A BLOCK_ERR is reported Clear block error cause The function block does not have a schedule downloaded Include block...

Страница 34: ...he device is defective LED Body temperature too high low The body temperature of the device exceeds its specification RB Alarm Concentrator BLOCK_ERR Resource block is in out of service mode The actua...

Страница 35: ...torage verification failed NV storage write failed Hardware error detected Channel 8 input failure Over underrange of measured value Wiring error Check transducer block for more details see manual Cha...

Страница 36: ...simulation possible Lost Static Data The database used for storing the NV parameters within the device is corrupt Device Needs Maintenance Now The hardware of the device failed in some way e g body te...

Страница 37: ...ms 22 MEMORY_SIZE Available configuration memory in the empty resource 23 NV_CYCLE_T Interval between writing copies of NV parameters to non volatile memory Zero means none 24 FREE_SPACE Percent of me...

Страница 38: ...bcode field The first alert to become active will set the Active status in the ALARM_STATE subcode 37 ALARM_SUM The current alert status unacknowledged states unreported states and disabled states of...

Страница 39: ...ultiple errors may be shown 07 PV EU of XD_SCALE The primary analog process variable used in block execution 08 OUT EU of OUT_SCALE or XD_SCALE if in direct L_TYPE The primary analog block output valu...

Страница 40: ...tatus in the ALARM_STATE subcode As soon as the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the subcode has chang...

Страница 41: ...of the block Actual The mode the block is currently in Target The mode to go to Permitted Allowed modes that target may take on Normal Most common mode for target 06 BLOCK_ERR This parameter reflects...

Страница 42: ...number of the plant unit This information may be used in the host for sorting alarms etc 05 MODE_BLK The actual target permitted and normal modes of the block Actual The mode the block is currently in...

Страница 43: ...nt in seconds of a first order lag filter applied to Primary value Valid values are 0 255 s A value of 0 disables filtering 13 Sensor Type S OOS Type of the attached sensor For a list of supported sen...

Страница 44: ...ibration for the attached sensor 23 RTD 2 Wire Resistance S OOS Specifies an offset subtracted from the measured resistance if a two wire RTD or Ohm sensor is attached The value is specified as a posi...

Страница 45: ...bration has been executed Failure The last user calibration failed The values are invalid The user calibrated measurement cannot be turned on The block will report a configuration error if Calibration...

Страница 46: ...K S W The actual target permitted and normal modes of the block Actual The mode the block is currently in Target The mode to go to Permitted Allowed modes that target may take on Normal Most common mo...

Страница 47: ...ng sensor block is in OOS mode 16 Sensor Diagnostics Channel 1 S W Allows to enable disable the sensor diagnostics for sensor 1 18 73 The sensor specific values above are repeated for the sensor input...

Страница 48: ...rl fuchs com Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check www pepperl fu...

Отзывы: