2
017-
05
30
Temperature Multi-Input Device
Troubleshooting
6.2
Resource Block
Problem
Remedy
Parameter
Message
Cause
Procedure
BLOCK_ERR Lost Static
Data
Parameterization data stored in
the device was faulty and was
replaced by default settings
Repeat parameterization. If
this error occurs repeatedly,
send the device to
Fuchs for repair
Device needs
maintenance
now
Hardware error
Send device to
Fuchs for repair
Simulate
active
Simulation enabled by setting
switch 1
Check whether simulation
is permitted
OOS
The target mode of the block is
OOS
Set block to "Auto" mode
RS_STATE
Online
No error
-
Stand–by
The target mode of the block is
OOS
Set block into "Auto" mode
Table 6.1
Resource block errors