IO-Link Parameterization
6
IO-Link Parameterization
Only the parameters of the ENA***TL-**IO** product group that require explanation are listed
below.
The abbreviations below are used in the following:
6.1
Config - ST Resolution
Configuration Singleturn Resolution
The "Config - ST Resolution" parameter is used to set the resolution of the rotary encoder. The
resolution refers to the singleturn resolution. Consequently, this value is used to set how many
equal-sized position steps are output/counted in one revolution.
The following figure illustrates this with an example for singleturn-only device versions.
Figure 6.1
Identical shaft position with different singleturn resolutions
A singleturn resolution of 1000 is selected on the left and 12,000 on the right. The physical
shaft position is the same on the left and right (see "shaft"). However, the "MDC1 - Position"
process data show different data on the left and right. This is explained by the division of a full
revolution into 1000 steps in one case and into 12,000 steps in the other.
The figure below illustrates this with an example for multiturn device versions.
Note
A comprehensive overview of all parameters for the respective absolute rotary encoder can be
found online at www.pepperl-fuchs.com. Navigate to the relevant product page for the
ENA***TL-**IO** and click on the corresponding "IO-Link parameter data sheet" document.
ro
read only
wo
write only
rw
read and write
Index
Sub
Parameter
Access
Data Type
Length
96 (0x60)
—
Config - ST Resolution
rw
UInteger
16 bits
0
0
shaft
3000
6000
9000
shaft
250
500
750
Index
Bitoffset
Parameter
Value
(Process data)
-
32
MDC1-Position
875
0x60
-
Config-ST Resolution 1000
Index
Bitoffset
Parameter
Value
(Process data)
-
32
MDC1-Position
10500
0x60
-
Config-ST Resolution 12000
Position
Singleturn version
Position
Singleturn version