DA5-IU-C

Seite 2

Operating instructions
Digital display with analogue inputs

Type DA5-IU-C

1.1 Safety instructions and warnings

Only use this display

– in a way according to its intended

purpose

– if its technical condition is perfect
– adhering to the operating 

instructions and the general 
safety instructions.

1.2 General safety instructions

1. Before carrying out any installation or mainte-

nance work, make sure that the power supply
of the digital display is switched off.

2. Only use this digital display in a way according

to its intended purpose: If its technical condi-
tion is perfect.Adhering to the operating in -
structions and the general safety instructions.

3. Adhere to country or user specific regulations.
4. The digital display is not intended for use in

areas with risks of explosion and in the
branches excluded by the standard EN 61010
Part 1.

5. The digital display should only operate if it has

been correctly mounted in a panel, in accor-
dance with the chapter “Technical features”.

1.3 Use according to the intended purpose

The digital display may be used only as a panel-
mounted device. Applications of this product may
be found in industrial processes and controls, in
manufacturing lines for the metal, wood, plastics,
paper, glass, textile and other processing indus-
tries.
Over-voltages at the terminals of the digital dis-
play must be kept within the limits in Category II

If the digital display is used to monitor machines
or processes in which, in case of a failure of the
device or an error made by the operator, there
might be risks of damaging the machine or caus-
ing accidents to the operators, it is your responsi-
bility to take appropriate safety measures.

1.4 Description

•   5digit digital display with analogue inputs
•   LED-Display with 8 mm high characters and

very high luminosity

•   Display range -19999..99999 with leading zero

blanking

•   Programming of functions and operating

parameters via the two setting keys. During
programming the display guides the user with
text prompts.

•   Programmable features:

    Range
    Max. value display yes/no
    Max. value reset yes/no
    Min. value display yes/no

Min. value reset yes/no

    Decimal point
    Min. input signal
    Displayed value at min. input signal
    Max. input signal
    Displayed value at max. input signal

2. Inputs

LATCH

(Connect 4)

Static input freezing the displayed value. 
If this input (pnp) is supplied with 
4 ... 30 V DC the actual value is frozen until the
input is released or the signal level gets below 2
V DC. The calculating of max. and min. value is
not af fec ted.

CURRENT INPUT

(Terminal 5)

Analogue current input with reverse connection
pro tec tion and current limitation to max. 50 mA.
Connect the signal line with the an sig-
nal with this input.

Caution:

To prevent interfering signals caused

by the supply voltage, this input is isolated from
the supply voltage. Thus, for the measurement,
connect the signal line with the most negative
signal to the analogue reference input.

VOLTAGE INPUT

(Terminal 7)
Analogue voltage input. Connect the signal line
with the an signal with this input. In case
of reverse connection, the display shows „Err4“.

!

Содержание DA5-IU-C

Страница 1: ...Digitalanzeige mit Analogausg ngen DA5 IU C FABRIKAUTOMATION SENSING YOUR NEEDS Bedienungsanleitung...

Страница 2: ...sch digung der Maschine oder ein Unfall des Bedienungsper sonals m glich ist dann m ssen Sie entsprechende Sicherheitsvor kehrungen treffen 1 4 Beschreibung 5stellige Digitalanzeige mit Analogeing nge...

Страница 3: ...ckt hal ten und Spannungsversorgung einschalten b Auf dem Display erscheint c Sobald die Tasten losgelassen werden er scheint im sek ndlichen Wechsel der Men ti tel und die aktuelle Men punkteinstell...

Страница 4: ...gssi gnal bei Messbereich 4 20 mA den hier eingestellten Wert wird lo angezeigt Unterschreitet das Eingangssi gnal bei Messbereich 2 10 V den hier eingestellten Wert wird lo angezeigt a b 4 8 Anzeigew...

Страница 5: ...mA Spannungsmessung Eingangswiderstand 1 M Max Spannung 30 V Netzbrummunterdr ckung digitale Filterung 50 Hz Spannungsversorgung 10 30 V DC galvanisch getrennt Stromaufnahme max 50 mA Umgebungstemper...

Страница 6: ...wert 80 zugeordnet Die Anzeige ist nun auf den Sensor abgestimmt und kann die jeweiligen Zwischen werte anzeigen 8 2 F llstandsmessung Ein F llstandssensor mit linearer Charakteristik unlinearen Senso...

Страница 7: ...DA5 IU C Seite 7 Schalttafelausschnitt 22 2 0 3 x 45 0 6 mm Einbaurahmen Senkung Af3 DIN 74 1 10 Abmessungen 22 2 0 3 45 0 6 deutsch...

Страница 8: ...Digital Display with Analogue Inputs DA5 IU C SENSING YOUR NEEDS FABRIKAUTOMATION...

Страница 9: ...or processes in which in case of a failure of the device or an error made by the operator there might be risks of damaging the machine or caus ing accidents to the operators it is your responsi bilit...

Страница 10: ...splay alternates between menu title and corresponding menu setting at a frequency of 1 Hz After any key is pressed only the menu setting is displayed d Pressing the right key will switch the menu sett...

Страница 11: ...V This menu title allows a limitation of the display range refrt to 4 7 and 9 4 a or b is selected depending on the chosen input range If with the input range 4 20 mA the input signal level exceeds t...

Страница 12: ...ing display values can be calculated Displayed value can be freely adjusted to the input value inside the display range Measuring rate 0 5 Measurement sec 2 Measurements sec Current measurement Voltag...

Страница 13: ...w lo 4 20 mA is chosen as input range Assign 0 as displayed value at min input signal to the lowest input level and 10 as displayed va lue at max input signal to the highest input level Additionally p...

Страница 14: ...DA5 IU C Seite 7 Front panel cut out 22 2 0 3 x 45 0 6 mm Bezel Countersinking Af3 DIN 74 1 10 DImensions 22 2 0 3 45 0 6...

Страница 15: ...L afficheur Digital entr es Analogiques DA5 IU C SENSING YOUR NEEDS FABRIKAUTOMATION...

Страница 16: ...sion II Si l afficheur digital est mis en oeuvre pour la surveillance de machines ou de process o en cas de panne ou d une erreur de manipulation de l appareil peuvent appara tre des risques de dommag...

Страница 17: ...ssoir de gauche Si ni l enre gistrement de la valeur maximum ni celui de la valeur minimum ne sont activ s les touches ne sont pas actives lorsque l appareil est en fonc tion 3 2 R glage des param tre...

Страница 18: ...e nombre de d cimales affich es 0 pas de d cimale 0 0 une d cimale 0 00 deux d cimales 0 000 trois d cimales 0 0000 quatre d cimales 4 7 Signal d entr e minimum uniquement dans la plage de mesure de 4...

Страница 19: ...u z ro automatique D rive due la temp rature 70 ppm K Vitesse de mesure 0 5 2 mesures sec Mesure en courant Chute de tension 2 0 V DC maximum 20 mA Courant max 50 mA Mesure en tension R sistance d ent...

Страница 20: ...capteur de niveau caract ristiques lin aires dans le cas de capteurs non lin aires il faut intercaler des l ments de lin arisation d livre 5 mA si le r servoir est vide et 19 mA s il est plein Il doit...

Страница 21: ...de 10 m3 Le volume de remplissa ge ne doit pas d passer 8 m3 et le contenu du r servoir ne doit pas descendre au dessous de 1 m3 Il faut donc afficher hi pour des valeurs 8 m3 et lo pour des valeurs 1...

Страница 22: ...DA5 IU C Seite 8 D coupe d encastrement 22 2 0 3 x 45 0 6 mm Cadre de montage Fraisure Af3 DIN 74 1 10 Dimensions 22 2 0 3 45 0 6...

Страница 23: ......

Страница 24: ...utomation The company is also setting standards in quality and innovative technology We develop produce and distribute electronic sensors and interface modules on a global scale By means of our world...

Отзывы: