Barcon LHC/PPC (HART)
Installation
D
a
te of Is
s
u
e
2
5.10.2001
15
Fig.2.5:
Barcon PPC-M10 with screwed or welded adapter. With screw adapter max. torque 80 Nm
2.3
Mounting instructions with diaphragm seal
Barcon
with diaphragm seal
– LHC-M40
The Barcon with diaphragm seal is screwed in, flanged or clamped, depending on the
type of diaphragm seal.
Fig.2.6:
Diaphragm seal versions
•
The protective cap of the diaphragm seal should only be removed just
before mounting in order to protect the diaphragm.
•
The diaphragm of the diaphragm seal of the Barcon must not be dented or
cleaned with pointed or hard objects.
•
The diaphragm seal and the pressure sensor together form a closed and
calibrated system which is filled with filling fluid through a hole in the upper
part of the sensor. The following rules should be observed:
- This hole is sealed and is not to be opened.
- The instrument should only be turned by the diaphragm seal at the point
provided and not by the housing.