AS-i 3.0 PROFINET Gateway in Stainless Steel
Configuration of AS-i/PROFINET Gateways
31
.1.
201
4
57
10.5
Safety Control/Status
In the fieldbus configuration the designator
Safety Control/Status
can be added
as cyclical data. This is possible both for the integrated Safety Monitor and for 2nd
generation Monitors.
The state of the outputs and the message outputs is then inserted as a cyclical in-
put datum.
Information!
Generation III external Monitors allow a maximum of eight OSSDs to be sent.
Inputs
byte
description
1
Status OSSD 1, color-coded as defined in the table <Coding of status
bytes>).
2
Status OSSD 2, color-coded as defined in the table <Coding of status
bytes>).
…
…
n
Status OSSD n, color-coded as defined in the table <Coding of status
bytes>).
Tab. 10-24.
Coding of status bytes
Bit [0 ... 3]
state or. color
description
00
16
green permanent ligh-
ting
output on
01
16
green flashing
delay time is running at stop category 1
02
16
yellow permanent ligh-
ting
start-up/restart-disable active
03
16
yellow flashing
external test necessary / acknowledge-
ment / start delay active
04
16
red permanent lighting
output off
05
16
red flashing
error
06
16
grey or off
output not projected
07
16
reserved
Bit [6]
status or color
0
no device flashing yel-
low
1
at least one device flas-
hing yellow
Tab. 10-25.