1 / 6
TTDM-128
TraceTek Leak DeTecTion MasTer MoDuLe insTaLLaTion insTrucTions
THERMAL MANAGEMENT SOLUTIONS
EN-TraceTekTTDM128-IM-H57341 03/13
GENERAL INfORMATION
Please read these instructions carefully and keep them in a safe
place (preferably close to the TTDM-128) for future reference.
These instructions must be followed carefully to ensure proper
operation.
The TTDM-128 Leak Detection Master Module has been designed
specifically for use with TraceTek sensing cables, point sensors,
sensor interface modules and relay modules. The TTDM-128 can
directly monitor up to 1500 m (5000 ft) of sensing cable, and large
networks of remote leak detection modules.
An external disconnect device and appropriate branch circuit
protection (no more than 20 amp rating) should be provided for
the TTDM-128. The disconnect device should be clearly marked
as such. Follow all national and local codes and regulations
applicable to the installation.
TOOLS REqUIREd
• Drill or hole punch for electrical conduit entries
• Phillips (cross-head) screwdriver
• Small flat-head screwdriver
INSTALLATION ITEMS (NOT SUppLIEd
)
• Wall fasteners for surface mounting (four screws)
STORAGE
Keep the module in a dry place prior to installation to avoid
possible damage to internal components.
pROdUcT INfORMATION
TTdM-128
115 Vac +15%, –20%; 50/60 Hz
230 Vac ±10%; 50/60 Hz
TTdM-128-24V
24 Vac +5%, –35% 24 Vdc ±20%
power consumption
10 VA for TTDM-128
12 VA for TTDM-128-24 V
Installation categories
Overvoltage Category II, Pollution Degree 2
Built-in relays
Number: Three (Service, Leak, Fault)
Type: DPDT
Rating:
5 A at 250 Vac/24 Vdc
Storage temperature
–18°C to 60°C (0°F to 140°F)
Operating temperature
0°C to 50°C (32°F to 122°F)
Enclosure
NEMA 12; IP 54
Shock hazard
. Shut off power before opening enclosure door.