background image

1 / 6

TTDM-128

TraceTek Leak DeTecTion MasTer MoDuLe insTaLLaTion insTrucTions

THERMAL MANAGEMENT SOLUTIONS

EN-TraceTekTTDM128-IM-H57341      03/13

GENERAL INfORMATION

Please read these instructions carefully and keep them in a safe 

place (preferably close to the TTDM-128) for future reference. 

These instructions must be followed carefully to ensure proper 

operation.
The TTDM-128 Leak Detection Master Module has been designed 

specifically for use with TraceTek sensing cables, point sensors, 

sensor interface modules and relay modules. The TTDM-128 can 

directly monitor up to 1500 m (5000 ft) of sensing cable, and large 

networks of remote leak detection modules.
An external disconnect device and appropriate branch circuit 

protection (no more than 20 amp rating) should be provided for 

the TTDM-128. The  disconnect device should be clearly marked 

as such. Follow all national and local codes and regulations 

applicable to the installation.

TOOLS REqUIREd

•  Drill or hole punch for electrical conduit entries

•  Phillips (cross-head) screwdriver

•  Small flat-head screwdriver

INSTALLATION ITEMS (NOT SUppLIEd

)

•  Wall fasteners for surface mounting (four screws)

STORAGE

Keep the module in a dry place prior to installation to avoid 

possible damage to internal components.

pROdUcT INfORMATION

TTdM-128

115 Vac +15%, –20%; 50/60 Hz 

230 Vac ±10%; 50/60 Hz

TTdM-128-24V

24 Vac +5%, –35%     24 Vdc ±20%

power consumption

10 VA for TTDM-128 

12 VA for TTDM-128-24 V

Installation categories

Overvoltage Category II, Pollution Degree 2

Built-in relays

Number:  Three (Service, Leak, Fault)

 

Type: DPDT 

Rating: 

5 A at 250 Vac/24 Vdc

Storage temperature

–18°C to 60°C (0°F to 140°F)

Operating temperature

0°C to 50°C (32°F to 122°F)

Enclosure

NEMA 12; IP 54

Shock hazard

. Shut off power before opening enclosure door.

WARNING:

AppROVALS ANd cERTIfIcATIONS

General Signaling Equipment

76LJ

TYPE NM

Отзывы: