background image

EN-TraceTekTT1100OHP-IM-H58263      01/15     

PN P000000886

THERMAL BUILDING & 

INDUSTRIAL HEAT TRACING SOLUTIONS

8 / 8

© 2008-2015 Pentair.

NORTH AMERICA 

Tel: +1.800.545.6258

Fax: +1.800.527.5703

Tel: +1.650.216.1526

Fax: +1.650.474.7215

[email protected]

EuROpE, MIddlE EAsT, AfRICA

Tel: +32.16.213.511

Fax: +32.16.213.603

[email protected]

AsIA pACIfIC

Tel: +86.21.2412.1688

Fax: +86.21.5426.2937

[email protected]

lATIN AMERICA

Tel.: +1.713.868.4800

Fax: +1.713.868.2333

[email protected]

Pentair and TraceTek are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the 

right to change specifications without prior notice.

symptom

possible cause and correction

Green LED not visible on TraceTek 

instrument

System is not powered. Check power wiring. Check circuit breakers that may have been 

tripped. On TTDM-128 check fuse and replace if necessary.

Leak alarm

(TTDM-128 message and red LED)

(SIM Red LED ON)

This is an indication of a LEAK event.

For leak locating modules (TTDM-128 and TTSIM-2): Using leak distance indication and System 

Map as a guide, investigate system condition, work to locate and repair leak.
For non-locating modules: Work to locate and repair the leak. (If your system is constructed 

with multiple sensor cable segments, using an end termination (TT-MET-PC) to break the sys-

tem into sections can help in locating the leak. Work outward from the alarm module using the 

end termination to establish a temporary end of the circuit, then sequentially move outward 

adding one cable segment at a time).
Once the leak is repaired, remove excess water from sensing cable and synthetic fiber jacket. 

Typically this will clear the Leak Alarm or LEAK condition (Red LED on SIM).
In order to clear the Service Req’d (or Service condition), moisture levels on sensor cable and 

synthetic fiber jacket need to be reduced with further drying.

note: When the service req’d or serVice condition exists (Yellow leD), leak location ac-

curacy is reduced for a new leak.

Yellow LED visible on TTC-1, TTSIM-1A,  

TTSIM-2 or flashing yellow LED on 

TTSIM-1

Could be cable break or service indication. Refer to alarm module instructions for more infor-

mation.
For Cable break indication:
Check for loose connectors, missing end terminations, broken jumper wires or physical dam-

age to the cable. Repair or replace cable if necessary. The TT-MET-PC end termination can 

be used to isolate a damaged section by working outward from the instrument using the end 

termination to establish a temporary end of the circuit then sequentially moving outward add-

ing one cable segment at a time.

“SERVICE Req'd” message  

(TTDM-128 Only)

This is an early warning message from the TTDM-128 panel indicating that the cable is becoming 

damp, but not yet to the level that constitutes a leak. The TTDM-128 panel may display a location 

in square brackets. If a location is displayed, that location should be investigated for possible 

sources of condensation/drips. The square brackets indicated that the leak signal is not strong 

enough for an accurate location calculation, so the indicated locations may include some error.

Red LED fails to turn off after leak is re-

paired, and leak alarm reset attempted

Cable and over-braid are still damp. Allow more time for cable to dry or investigate leak site to 

make sure that water is not pooling under or behind the sensor cable.

Leak location seems inaccurate in 

actual leak situation

More that one leak may be present or the cable may be damp in several locations. If the sys-

tem is monitored by a TTDM-128, check the event history to see if there is an earlier indica-

tion of a nearby leak or a SERVICE NEEDED message. If necessary use the end termination 

to break the system into smaller segments and work outward to isolate each leak location in 

multiple leak scenarios.

Leak locations seem inaccurate or 

unstable during mapping tests

Make sure that the simulated leak (MAPPING CAP) is kept in place for at least 30 seconds. The 

location circuitry in the instruments require a steady leak location in order to compute an accurate 

distance. Removing the simulated leak too quickly induces a random error.

troubleshooting

WWW.pENTAIRTHERMAl.COM

Содержание TraceTek TT1100-OHP

Страница 1: ...esigned for testing and troubleshooting TraceTek systems Digital multimeter Can be used as an alternative or supplement to the PTB Meter must have 20 MΩ range TT MAPPING CAP PC PN P000000872 Used to simulate leaks at connector points during commissioning and mapping process Extra TT MLC PC PN 683262 000 Leader cable Used with the ohmmeter to make easier connections to the sensor cable for resistan...

Страница 2: ...here hold down clips will be placed so adhesive can work properly Position hold down clips so the sensing cable will provide the desired leak detection coverage To best secure the cable alternate the direction of the hold down clips and install them at intervals of no greater than 6 feet 2 m and at every change in direction at sides of trench for example Important Let the adhesive dry per manufact...

Страница 3: ...ps off the bottom of the pipe or fitting Do not install the cable on the top or side surface of a pipe Do not spiral the cable on horizontal pipe Exception If the cable is used to trace vertical pipe the cable should be spiraled around the pipe and secured with tie wraps B For sumps containment trenches and subfloor applications Pull the cable alongside the installed hold down clips minimum bend r...

Страница 4: ...ing Cable Test Procedure 3 Connect the sensing circuit to the TraceTek alarm module and activate the system as soon as is practical Use the alarm module to monitor the sensing cable during the final stages of construction Take precautions if installation is incomplete at end of work day At the end of the work day Ensure that there are no open connectors Each sensing cable should be connected to a ...

Страница 5: ...A use the PTB to locate the liquid or contamination and take appropriate corrective action Method with Ohmmeter 1 Ensure the end termination is connected to the sensing cable If checking several lengths of sensing cable in series a cable string ensure they are all connected 2 Connect a Modular Leader Cable TT MLC PC to the sensing cable 3 Verify that the sensing cable is intact Loop 1 Measure the ...

Страница 6: ...e to have TT MBCs installed on branches as needed to fully trace a pipe system D Install an end termination TT MET PC at the end of the main line and each branch line Note A good check on the system design and bill of materials is that the total number of end terminations installed in the system should equal the number of branch connectors plus one E Optional Install jumper cables TT MJC xxx PC as...

Страница 7: ...a channel number and display the words SYSTEM NORMAL If the Yellow LED is on in any of these instruments or the words Cable Break or Loop Break is displayed then the cable system must be inspected for loose connections missing end terminations until the cable continuity is established and the Normal condition is achieved LEAK testing can be done with a mapping cap TT MAPPING CAP PC The MAPPING CAP...

Страница 8: ...uced for a new leak Yellow LED visible on TTC 1 TTSIM 1A TTSIM 2 or flashing yellow LED on TTSIM 1 Could be cable break or service indication Refer to alarm module instructions for more infor mation For Cable break indication Check for loose connectors missing end terminations broken jumper wires or physical dam age to the cable Repair or replace cable if necessary The TT MET PC end termination ca...

Отзывы: