Immediately after applying power, the evaporator blower (enclosure air) should start 

running. Operate the air conditioner with the compressor running for five (5) to ten 

(10) minutes. You will need to set the cooling controller set point below the ambient 

temperature to operate the compressor.
Condenser air temperatures should be warmer than normal room temperatures 

within a few minutes after the condenser impeller(s) starts.
If electrical power to the air conditioner is interrupted and reapplied, the compressor 

may take up to five (5) minutes to restart due to the high back pressure of the 

compressor.

DOOR SWITCH

The door switch terminal block on the back of the unit includes a jumper that is used 

only if the door switch option is not used. Several door switches may be connected 

in series and operated on one cooling unit. The door switch only supports a floating 

connection, no external voltages. Remove the jumper from terminals 3 and 4 of the 

connector, and connect the door switch to the two terminals if the door switch is 

available.

SURFACE MOUNTING

Air conditioner must be in upright position during operation. 

CAUTION

1.  Using the mounting gasket kit provided with the unit, install gasket to the air 

conditioner, see Figure 3.

2.  See Figure 5 or Figure 6 or Figure 7 or Figure 8 or Figure 9 for the enclosure 

cutout diagrams, depending on the unit being installed.

3.  Screw the supplied grub screws into the blind nuts on the rear of the unit, see 

Figure 4.

4.  Secure the unit using the supplied washers and nuts.

5.  Mount the air conditioner to the enclosure being careful not to damage the 

mounting gasket. The mounting gasket is the seal between the air conditioner 

and the enclosure. Avoid dragging the air conditioner on the enclosure with the 

mounting gasket attached as this could cause rips or tears in the gasket.

6.  Allow unit to remain upright for a minimum of five (5) minutes before starting.

Figure 3

Figure 4

SMART CONTROLLER

The controller is wired and programmed at the factory to be energized when power is 

applied to the air conditioner. Adjust the controller to the desired cabinet temperature.
The factory default cooling differential for controllers that are set-up for °C, or for °F, 

are as follows:

Cooling Set-point

Turn-on

Turn-off

35°C

35°C

30°C

80°F

87°F

80°F

Содержание SPECTRACOOL series

Страница 1: ... 2014 Pentair Equipment Protection www pentairprotect com 89113977 Rev B P N 89113978 SPECTRACOOL Slim Fit Air Conditioners Surface Mount Units Only QUICK START OPERATION GUIDE ...

Страница 2: ...wer supply using copper conductors only Power supply wiring should be restrained after field installation to ensure no contact with internal fan Minimum circuit ampacity should be at least 125 of the amperage and 10 of the voltage shown on the unit nameplate No other equipment should be connected to this circuit to prevent overloading Use a higher ampere rated circuit breaker or time delay fuse th...

Страница 3: ...ls if the door switch is available SURFACE MOUNTING Air conditioner must be in upright position during operation CAUTION 1 Using the mounting gasket kit provided with the unit install gasket to the air conditioner see Figure 3 2 See Figure 5 or Figure 6 or Figure 7 or Figure 8 or Figure 9 for the enclosure cutout diagrams depending on the unit being installed 3 Screw the supplied grub screws into ...

Страница 4: ... 44 280 11 02 550 21 65 8 4 315 196 7 74 Figure 5 S06 300W Surface Mount Cutout Dashed Lines Represent the Air Conditioner 267 10 50 203 8 00 188 7 40 192 7 56 13 50 262 2 10 32 306 12 05 532 2 20 94 280 11 02 550 21 65 8 4 315 Figure 6 S06 500W Surface Mount Cutout Dashed Lines Represent the Air Conditioner ...

Страница 5: ...385 2 15 16 400 15 75 951 37 44 10 8 375 Figure 7 S10 1000 1500W Surface Mount Cutout Dashed Lines Represent the Air Conditioner 356 14 00 310 12 19 400 15 75 280 5 11 02 316 12 44 651 25 63 240 9 44 554 21 83 275 2 10 82 325 2 12 80 550 2 21 65 380 2 14 96 1580 62 19 10 10 375 Figure 8 S16 2000 2500W Surface Mount Cutout Dashed Lines Represent the Air Conditioner ...

Страница 6: ...ect com 89113977 6 500 19 69 1580 62 19 456 17 94 410 16 13 380 5 14 96 316 12 44 693 27 30 164 6 46 499 19 66 275 2 10 82 375 2 14 77 500 2 19 68 380 2 14 96 10 10 375 Figure 9 S16 4000W Surface Mount Cutout Dashed Lines Represent the Air Conditioner ...

Отзывы: