GENERAL INFORMATION

4

  

PN1053 (06-10-20)

INTRODUCTION

Pentair Pentek® Defender provides control of high voltage 
(120/240 VAC) pumps.  Pump operations can be controlled 
through a mobile device or computer. 

The Pentek Defender is designed to provide superior protection 
for the water pump system.  Going beyond simple pressure 
switch function, the Pentek Defender constantly monitors 
cycle rate, pressure, current, and voltage.  When issues are 
detected, the Pentek Defender takes action to notify the owner 
or authorized dealer.

In addition to superior protection, the Pentair Pentek Defender 
is easy to set up and adjust.  Instead of turning screws to modify 
setpoint and differential, changes are programmed directly with 
any mobile device, tablet, or laptop.  The same interface offers 
easy access for fixing settings for incidents like dry run and 
excessive run time.

 

TECHNICAL SPECIFICATIONS

Input Power

120/240V, Single Phase

Operating Current

12A Max

Frequency

50/60Hz

Enclosure Rating

NEMA 3R

1

Maximum System Operating Pressure

100psi

1 When watertight conduit connectors are used.

 

LEDS

Power/Status:

 Indicates if the device has power or is faulted.

Connection:

 Indicates the status of the wireless connection.

POWER/STATUS

CONNECTION

Off

There is no 

power to the 

unit.

Off

There is no power to the 

unit.

Solid Red

There is power 

to the unit but it 

has faulted.

Blinking 

Blue

The unit is in local wifi 

access mode.

Solid 

Green

There is power 

to the unit and 

it is operating 

normally.

Solid Blue

The unit is connected to 

a local phone, tablet, or 

computer.

Blinking 

Green

Pump is 

running.

Blinking 

Green

The unit is connected to 

the home wifi network.

Solid 

Green

The unit is connected to 

the Internet.

Solid Red

The unit is not connected 

to any wifi and is searching 

for the home network.

Blinking 

Red

The unit is scanning for 

available wifi networks.

Pre-installation

 EXPLOSION HAZARD:

 

When the well tank has 

been in service and a change to a higher pre-charge pressure 
is necessary due to a required change in the pressure switch 
setting, failure to follow the below instructions can cause a 
rupture or explosion, possibly causing serious personal injury or 
death, and/or property damage.

 

Do not adjust or add pressure if there has been a loss of air.

 

Do not adjust the pre-charge pressure if there is visible 
exterior corrosion.

 

Do not adjust the pre-charge pressure if there has been a 
reduction of the pump cycle time or the pre-charge pressure 
compared to its initial setting. This is because a reduction 
in pump cycle time can result from loss of tank air pressure 
which may indicate the presence of internal corrosion. 
Any re-pressurization or additional pressure could result in 
rupture or explosion.

 

Do not use with components or materials that are 
incompatible with the unit.

PlumbIng

1.  The unit should be mounted as close as possible to the 

pressure tank.

         

 

Locate the unit following all local codes. Do not 

         locate the unit where it can be affected by flooding.

2.  You may assemble the unit using a 1/4”NPT pipe nipple to a 

“Tank Tee” or “Tank Cross” or adapt the unit to an in-line pipe 
fitting.  Use pipe sealing tape or pipe sealant. Tighten the unit 
using the wrench flats provided on the bottom connection.  

NOTE: 

DO NOT EXCEED 15 LB./FT. of torque.

 

NOTE:

 

Do not allow pipe sealant or other contaminants to 

enter the small port in the unit connection.

  

NOTE:

 

A mechanical pressure gauge is not required. Use the 

appropriate plug to block any unused ports.

Wiring

Install, ground, wire and maintain device in accordance with your 
local electrical code and all other codes/ordinances that apply. 
Consult your local building inspector for local code information.

Ground device permanently using wire of size and type specified 
by approved local or national codes.

 Risk of explosion. Do not ground to gas supply line.

NOTE: 

Connect ground wire first. Connect to ground first, then to 

green grounding wire provided in the device. Ground connection 
MUST be made to this wire. Do not connect motor to electrical 
power supply until unit is permanently grounded; otherwise 
serious or fatal electrical shock hazard may result.

For best ground connection, connect to grounded lead in service 
panel or to metal underground water pipe or well casing at 
least 10 ft. long. If plastic pipe or insulated fittings are used, run 

Содержание PENTEK DEFENDER CSC-LINK

Страница 1: ...pentair com INSTALLATIONAND OPERATIONMANUAL PN1053 06 10 20 2020 Pentair All Rights Reserved DEFENDER CSC LINK ENGLISH 3 10 ESPANOL 11 19 FRANCAIS 20 28 PENTEK ...

Страница 2: ... 3 4 Installation 5 7 Troubleshooting 8 9 Warranty 10 ESPANOL SECCIÓN PÁGINA Información general 12 13 Instalación 14 16 Solución de problemas 17 18 Garantía 19 FRANCAIS SECTION PAGE Informations générales 21 22 Installation 23 25 Dépannage 26 27 Garantie 28 ...

Страница 3: ...re differential An improperly sized tank can cause the pump to cycle and lead to pump damage This may require a larger pressure tank than is normally used CALIFORNIA PROPOSITION 65 WARNING This product and related accessories contain chemicals known to the State of California to cause cancer birth defects or other reproductive harm ELECTRICAL SAFETY ELECTROCUTION HAZARD Must be installed by a qual...

Страница 4: ... the below instructions can cause a rupture or explosion possibly causing serious personal injury or death and or property damage Do not adjust or add pressure if there has been a loss of air Do not adjust the pre charge pressure if there is visible exterior corrosion Do not adjust the pre charge pressure if there has been a reduction of the pump cycle time or the pre charge pressure compared to i...

Страница 5: ...of size and type specified by approved local or NEC national codes connect power supply leads to switch terminals marked LINE See Figure 1 and Table 1 4 Using the included wires and wire nuts of size and type specified by approved local or national codes connect motor leads to switch terminals marked MOTOR See Figure 1 and Table 1 5 Replace device cover 6 Pentair Pentek Defender is now wired for o...

Страница 6: ...any web browser i e Chrome Safari etc on your mobile device to pair the Pentek Well Defender to the router 7 Type 192 168 1 1 into the address bar and press enter This will take you to the main page for pairing the unit and mobile device 8 Click on Settings 9 Select the router from the drop down SSID list and enter the router password into the security key field Passwords are case sensitive 10 Cli...

Страница 7: ...me Seconds 30 1 65000 Time the device takes to recognize Dry Run condition Pressure psi 0 100 Displays the actual system pressure at the point of last data retrieval PARAMETER LIST Figure 3 System Settings Online Device Registration 1 Download the App to your mobile device from Apple App Store or Google Play 2 Open the App Existing users Login to your account click DEVICES and then ADD NEW DEVICE ...

Страница 8: ...s found during this step populate the SSID drop down during the setup process The unit is in local wifi access mode and is ready to be connected to a phone tablet or computer The unit is connected to a local phone tablet or computer The unit is connected to the home wifi network It will change to Solid Green when it connects to the internet and product servers If the device is not already register...

Страница 9: ...resistance Ohms and confirm they match motor specifications Rx1 scale Shorted motor wires line to ground Damaged wire insulation Check motor wire insulation with a megger Recommend a meter that can read values 2 000 000 Ohms or more Over Pressure System pressure exceeded the Over Pressure limit set in the device Setpoint changed to be too close to Over Pressure setting Recommend at least a 10psi d...

Страница 10: ...warranty will not apply to any product that in our sole judgment has been subject to negligence misapplication improper installation or improper maintenance Without limiting the foregoing operating a three phase motor with single phase power through a phase converter will void the warranty Note also that three phase motors must be protected by three leg ambient compensated extra quick trip overloa...

Страница 11: ...pentair com MANUALDEINSTALACIÓN YOPERACIÓN PN1053 06 10 20 2020 Pentair Todos los derechos reservados DEFENDER CSC LINK PENTEK ...

Страница 12: ...provocar daños en la bomba Esto puede requerir un tanque de presión más grande que el que se usa normalmente ADVERTENCIA DE PROPUESTA 65 DE CALIFORNIA ADVERTENCIA Este producto su embalaje y sus componentes contienen sustancias químicas que según el Estado de California provocan cáncer defectos de nacimiento o afectan a la fecundidad SEGURIDAD ELÉCTRICA PELIGRO PELIGRO DE ELECTROCUCIÓN Debe ser in...

Страница 13: ...n cambio requerido en la configuración del interruptor de presión el incumplimiento de las instrucciones a continuación puede causar una ruptura o explosión posiblemente causando lesiones personales graves o muerte y o daños a la propiedad No ajuste ni agregue presión si ha habido una pérdida de aire No ajuste la presión de precarga si hay corrosión exterior visible No ajuste la presión de precarg...

Страница 14: ...Pentek Defender requiere dos sencillos pasos para ponerlo en servicio Registro en línea y conexión WiFi NOTA Es importante que los pasos de puesta en marcha se realicen en el orden indicado en este manual El dispositivo puede emparejarse y controlarse desde un teléfono inteligente tableta o computadora El teléfono inteligente la tableta o la computadora que desea utilizar para emparejar el Pentair...

Страница 15: ...ectado con el dispositivo Pentek Well Defender 6 Abra cualquier navegador de Internet como Chrome Safari etc en su dispositivo digital móvil para conectar Pentek Well Defender al router 7 Escriba 192 168 1 1 en la barra de dirección y oprima Enter ingresar Esto le llevará a la página principal para conectar la unidad y el dispositivo digital móvil 8 Haga clic en Settings configuración 9 Seleccione...

Страница 16: ...a que funciona en seco Tiempo de detección del funcionamiento en seco Segundos 30 1 65000 El tiempo que le toma al dispositivo reconocer la condición de funcionamiento en seco Presión psi 0 100 Muestra la presión actual del sistema en la última recuperación de datos LISTA DE PARÁMETROS Figura 3 Configuración del sistema Registro del dispositivo en línea 1 Descargue la aplicación a su dispositivo d...

Страница 17: ...s durante este paso llenan el menú desplegable SSID durante el proceso de configuración La unidad está en modo de acceso wifi local y está lista para conectarse a un teléfono tableta o computadora La unidad está conectada a un teléfono tableta o computadora local La unidad está conectada a la red wifi doméstica Cambiará a Verde sólido cuando se conecte a Internet y a los servidores del producto Si...

Страница 18: ...las especificaciones del motor Escala Rx1 Cables de motor en cortocircuito línea a tierra Aislamiento de alambre dañado Verifique el aislamiento del cable del motor con un megóhmetro Recomiende un medidor que pueda leer valores de 2 000 000 ohmios o más Sobre presión La presión del sistema excedió el Límite de sobrepresión establecido en el dispositivo El punto de ajuste cambió para estar demasiad...

Страница 19: ...ásicos se deben proteger con relés de tres patas compensación ambiental y activación extra rápida del tamaño recomendado o la garantía se anulará Su único recurso y la única obligación de PENTAIR es que PENTAIR repare o reemplace los productos defectuosos a preferencia de PENTAIR Usted debe pagar todos los costos de labor y envío asociados con esta garantía y debe solicitar el servicio de garantía...

Страница 20: ...pentair com MANUELD INSTALLATION ET D UTILISATION PN1053 06 10 20 2020 Pentair Tous les droits sont réservés DEFENDER CSC LINK PENTEK ...

Страница 21: ...et l endommager Cela peut nécessiter un réservoir sous pression plus grand que celui utilisé normalement AVERTISSEMENT CALIFORNIE PROPOSITION 65 AVERTISSEMENT Ce produit et ses accessoires contiennent des produits chimiques connus dans l État de Californie pour causer le cancer des malformations congénitales ou d autres problèmes de reproduction SÉCURITÉ ÉLECTRIQUE DANGER DANGER D ÉLECTROCUTION Do...

Страница 22: ...age du pressostat le non respect des instructions ci dessous peut provoquer une rupture ou une explosion pouvant entraîner des blessures graves ou la mort et ou des dommages matériels Ne pas ajuster ou ajouter de pression s il y a eu une perte d air Ne pas régler la pression de précharge en présence de traces de corrosion visibles de l extérieur Ne pas régler la pression de précharge s il y a eu u...

Страница 23: ...la mise en service l inscription en ligne et une connexion Wi Fi REMARQUE Il est important que les étapes de mise en service soient effectuées dans l ordre indiqué dans ce manuel L appareil peut être couplé et contrôlé avec un téléphone intelligent une tablette ou un ordinateur Le téléphone intelligent la tablette ou l ordinateur que vous souhaitez utiliser pour coupler le Pentair Pentek Defender ...

Страница 24: ...teur Web Chrome Safari etc sur l appareil mobile pour jumeler le Pentek Well Defender au routeur 7 Taper 192 168 1 1 dans la barre d adresse et appuyer sur Entrée Cela vous dirigera à la page principale de jumelage du dispositif et de l appareil mobile 8 Cliquer sur Paramètres 9 Sélectionner le routeur dans la liste déroulante SSID et entrer le mot de passe du routeur dans le champ de la clé de sé...

Страница 25: ...tion Time durée de détection Secondes 30 1 65000 Temps nécessaire au dispositif pour reconnaître l état de Dry Run fonctionnement à vide Pression psi 0 100 Affiche la pression réelle du système au point de la dernière récupération de données LISTE DES PARAMÈTRES Figure 3 Paramètres système Enregistrement du dispositif en ligne 1 Télécharger l application sur votre appareil mobile à partir de l App...

Страница 26: ...plissent le menu déroulant SSID lors du processus de configuration L unité est en mode d accès wifi local et est prête à être connectée à un téléphone une tablette ou un ordinateur L unité est connectée à un téléphone local une tablette ou un ordinateur L unité est connectée au réseau wifi de la maison Le témoin passera au vert fixe lorsqu il se connectera à Internet et aux serveurs de produits Si...

Страница 27: ...assurer qu elle correspond aux spécifications du moteur Échelle Rx1 Fils de moteur en court circuit ligne à terre Isolation de fil endommagée Vérifier l isolation du fil du moteur avec un appareil Megger Recommandé un compteur pouvant lire des valeurs de 2 000 000 ohms ou plus Surpression La pression du système a dépassé la limite de surpression définie dans l appareil Le point de consigne a chang...

Страница 28: ...PENTAIR répare ou remplace les produits défectueux au choix de PENTAIR Vous devez payer tous les frais de main d œuvre et d expédition associés à cette garantie et demander le service de garantie par l entremise du concessionnaire installateur dès qu un problème est découvert Aucune demande de service ne sera acceptée si elle est reçue après l expiration de la période de garantie Cette garantie n ...

Отзывы: