10-1008-194 Rev. 2 

 

Page 7 

high compressor operating temperature causes automatic shut-down of the unit. The above described 
shut-down is symptomatic of a clogged or dirty filter, thus causing a reduction in cooling airflow across the 
surface of the compressor and condenser coil. 

 

Do not run the air conditioner for extended periods of time with the filter removed. Particles of dust, lint, 
etc., can plug the fins of the condenser coil which will give the same reaction as a plugged filter. The 
condenser coil is not visible through the filter opening, so protect it with a filter. 

 

Continued operation under the above conditions can and will damage and shorten compressor life. The 
air conditioner is available with an easily removable inlet filter to facilitate necessary cleaning. There 
should be no reason to neglect this necessary maintenance. 

 

How To Remove, Clean or Install a New Inlet Air Filter 

 

RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust 
holding capacity and a minimum amount of resistance to air flow. Because they are constructed entirely 
of aluminum they are lightweight and easy to service. Optimum filter performance is maintained by 
recoating the filters after washing with RP Super Filter Coat adhesive. To achieve maximum performance 
from your air handling equipment, air filters should be cleaned on a regular basis. 

 

The inlet air filter is located behind the front cover. To access filter, pull ring protruding from slot in bottom 
of front cover. The filter may now be cleaned or new filter installed. 

 

Cleaning Instructions: 
1. Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS. 

 

2. After flushing allow filter to drain. Placing it with a corner down will assure complete drainage. 

 

3. Recoat the filters with RP Super Filter Coat adhesive. When spraying filter do so from both sides for 
maximum concentration of adhesive. 

 

Condenser and Evaporator Fans 

 

Fan motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the 
life of the fan.  

 

Caution: Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly 
deteriorate filters, condenser coils, fans and motors, etc. Contact McLean Thermal for special 
recommendations. 

 

Refrigerant Loss 

 

Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks. 
Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection 
equipment during manufacture may require repair or recharging of the system. This work should only be 
performed by qualified professionals, generally available through a local, reputable air conditioning repair 
or service company. 

 

Refer to the data on the nameplate which specifies the type of refrigerant and the charge size in ounces. 

 

Before recharging, make sure there are no leaks and that the system has been properly evacuated into a 
deep vacuum.

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-5882-Hoffman-T150126G100-T-Series-AC-230V-900-BTU-Outdoor.aspx

Содержание McLean THERMAL T15 Series

Страница 1: ...cLean Thermal 11611 Business Park Blvd N Champlin MN 55316 Tel 763 323 8200 Fax 763 576 3200 www mcleanthermal com RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 5882 Hoffman T150126G100 T Series AC 230V 900 BTU Outdoor aspx ...

Страница 2: ...m with the delivering carrier McLean Thermal cannot accept responsibility for freight damages however we will assist you in any way possible HANDLING TESTING THE AIR CONDITIONER If it is necessary to place the air conditioner in a horizontal position after unpacking be certain it is placed in an upright vertical or mounting position for a minimum of five 5 minutes before operating Never attempt to...

Страница 3: ... has cooled to within the thermal overload cut in temperature setting INSTALLATION Step 1 Inspect air conditioner Verify functionality before mounting the air conditioner see Handling Testing the Air Conditioner on page 1 Step 2 Using the cutout dimensions shown in this manual prepare the air IN and air OUT openings and mounting bolt hole pattern for the enclosure Step 3 Using the gasket kit provi...

Страница 4: ...6 1 800 131 55 27 12 3 T15 0116 GXXX 100 50 3 8 1 800 125 52 27 12 3 T15 0126 GXXX 230 60 1 5 1 900 131 55 27 12 3 T15 0126 GXXX 220 50 1 4 1 800 125 52 27 12 3 XXX will be replaced with a three digit number designating all desired options Consult the factory for specific model numbers T15 Model Drawing RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 5882 Hoffman T150126G100 T ...

Страница 5: ...1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 10 1000 91 10 1000 91 Filter Dryer 52 6028 03 52 6028 03 Freeze stat 10 1033 26 10 1033 26 Service Cord 52 6035 138 52 6035 139 Terminal Block 10 1003 03 10 1003 03 Thermal Overload Compressor 10 1007 67 10 1007 68 Thermostat SPST 55 100F 10 1061 02 10 1061 02 RSPSupply 1 888 532 2706 www...

Страница 6: ...10 1008 194 Rev 2 Page 5 T15 Wire Diagram T15 Schematic RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 5882 Hoffman T150126G100 T Series AC 230V 900 BTU Outdoor aspx ...

Страница 7: ...ould provide years of satisfactory operating service Should the refrigerant charge be lost recharging ports access fittings on the suction and discharge sides of the compressor are provided for recharging and or checking suction and discharge pressures Under no circumstances should the access fitting covers be loosened removed or tampered with Breaking of seals on compressor access fittings during...

Страница 8: ...cess filter pull ring protruding from slot in bottom of front cover The filter may now be cleaned or new filter installed Cleaning Instructions 1 Flush the filter with warm water from the exhaust side to the intake side DO NOT USE CAUSTICS 2 After flushing allow filter to drain Placing it with a corner down will assure complete drainage 3 Recoat the filters with RP Super Filter Coat adhesive When ...

Страница 9: ...or Obstructed blades 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm YES wait 5 minutes then proceed to step 7 NO possible Defective thermostat Defective capacitor Defective overload Defective relay 7 Make sure the coils are clean Then check evaporator air in and air out temperatures If the temperatures are the ...

Страница 10: ...essor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Under sized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical information i e amp draw pressures temperatures contact McLean Thermal at 763 323 8200 RSPSup...

Страница 11: ...r warranty consideration Please be advised According to the Federal Register no person maintaining servicing repairing or disposing of appliances may knowingly vent or otherwise release into the environment any class I or class II substance used as refrigerant McLean Thermal assumes no liability beyond the repair or replacement of its own product Customer modification of any McLean Thermal product...

Отзывы: