Figure 1.

Connection

for Service

Gas Category, Type and Supply Pressure Range

The heater gas category, type and supply pressure range is as follows:

             

 G20 @ 20 mbar

                      G31 @  37 mbar

WARNING

 Risk of fire and explosion.

 Improper installation, incorrect adjustment, alteration, service, or maintenance of the Combination

 Gas Control Valve can lead to fire or explosion, causing loss of life, personal injury, and/or property damage. If it is necessary
 to adjust the gas valve, this must be done by only by a qualified service agency. These instructions are for the use of qualified
 service technicians only! Do not attempt this procedure unless you have been trained and certified in the care and repair of
 gas-fired appliances! Do not attempt this procedure if you find the following instructions confusing!

This appliance is equipped with an unconventional gas control valve that is factory set with a manifold pressure of 110 ± 50
mbar (11 ± 5 kPa). Installation
or service must be performed by
a qualified installer, service
agency, or the gas supplier. If
this control valve is replaced, it
must be replaced with an
identical control.The combination
gas valve incorporates dual shut-
off valves and a negative-
pressure regulator. For proper
operation, the regulated pressure
at the outlet manifold of the valve
must be 110 ± 50 mbar
(11 ± 5 kPa) below the reference
pressure at the blower mixer inlet,
and the gas valve ‘VENT’ tap
must be connected to the end cap
air orifice as shown in Figure 1.

DO

NOT  attempt to adjust  the gas
input by adjusting the regulator
setting. The correct gas regulator
setting is required to maintain proper combustion and must NOT be altered.

Connection

for Test

Instructions for Checking the Gas Pressure through the Combination Gas Control Valve

Gas Orifice Replacement Kit Installation Instructions

Before proceeding with adjustment, verify that the letter codes stamped on the orifices correspond to the letter code for your
model shown on the Parts List, 

Page 4

.

Required Tools:

 The following tools and instruments are rquired to make the adjustment:

1 Adjustable wrench, 2-1/2" (65 mm) Capacity
1 Adjustable wrench, 1-1/2" (39 mm) Capacity
1 Flat Blade Screwdriver
1 Small flat head screwdriver for set-screw in gas valve
1 7/16" (11 mm) Nut Driver
1 7/16" (11 mm) Wrench
2 610 mm (2 ft.) lengths of flexible plastic or rubber tubing
1 1/8" barbed Tee fitting
1 Pipe Sealant approved for use with Natural Gas or LPG
1 Differential pressure gauge or slope gauge (inclined manometer)

capable of reading to a resolution of 1.0 kPa (the “Low Pressure Gauge”)

1 Flue-gas analyzer reading CO

2

2 305 mm (12") lengths of 3.4 mm (1/4") flexible plastic tubing

Do not attempt the orifice replacement without all the listed tools and instruments.

II

2H3P

Содержание MASTERTEMP

Страница 1: ...ater contains carbon monoxide a dangerous poisonous gas you cannot see or smell Symptoms of carbon monoxide exposure or poisoning include dizziness headache nausea weakness sleepiness musculartwitching vomitingandinabilitytothinkclearly IFYOUEXPERIENCE ANY OF THE ABOVE SYMPTOMS IMMEDIATELY TURN OFF THE POOL HEATER LEAVE THE VICINITY OF THE POOL OR SPA AND GET INTO FRESH AIR IMMEDIATELY THE POOL HE...

Страница 2: ...ves and a negative pressure regulator For proper operation the regulated pressure at the outlet manifold of the valve must be 110 50 mbar 11 5 kPa below the reference pressure at the blower mixer inlet and the gas valve VENT tap must be connected to the end cap air orifice as shown in Figure 1 DO NOT attempt to adjust the gas input by adjusting the regulator setting The correct gas regulator setti...

Страница 3: ...e tap 11 Open the gas supply to the heater 12 Verify that the seal connection in the pressure tap is closed by testing for leaks with soapy water Note If the pressure reading is out of range regulate the incoming gas pressure see Table below Table 1 Inlet Gas Pressure Requirements e r u s s e r P s a G m u m i n i M m u m i x a M s a G l a r u t a N r a b m 0 1 a P k 0 1 r a b m 0 6 a P k 0 6 s a ...

Страница 4: ...bel from Step 11 Remove Orifice 2 5X Install O Ring and new Orifice then Reconnect the Gas Line Union Figure 3 Install new Orifice and Reconnect Union Kit No Model No ID Stamp 474142 200HD Convert NG to LP LQ 474141 300HD Convert NG to LP LN 474140 400HD Convert NG to LP LK 474145 200HD Convert LP to NG NH 474144 300HD Convert LP to NG NE 474143 400HD Convert LP to NG NB Fuel Gas Conversion Kits N...

Страница 5: ... backing strip and apply the label with uniform pressure over the entire surface see Figure 4 APPELER LE SERVICE A LA CLIE POUR VALIDER VOTRE GARA FOR CUSTOMER SERVIC CALL OU POUR 1 800 831 7133 COMPOSEZ LE 1 800 831 7133 OR ge MOORPARK CA 93021 FOR YOUR SAFETY Specifications Inlet Pressure Natural Gas Propane Gas Max 60 mbar 6 0 kPa 60 mbar 6 0 kPa Min 10 mbar 1 0 kPa 25 mbar 2 5 kPa Manifold Pre...

Страница 6: ...6 Blank Page ...

Страница 7: ...7 Blank Page ...

Страница 8: ...s that may be used in this document are not used to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Water Pool and Spa Inc Those names and brands may be the trademarks or registered trademarks of those third parties Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice...