manualshive.com logo in svg
background image

3

Rail Support Brackets:

The TL lift-outs are designed to 

use 2" standard pipe for guide 

rails. A top rail support bracket 

is available to be mounted to 

the hatch frame. Intermediate 

brackets are available for deep 

basins. It is recommended that if 

the rail length is over 21', that an 

intermediate bracket be installed. 

After every additional 20' of rail, 

another intermediate bracket 

should be used for proper rail 

support.
Basin Covers:

Hydromatic has several types of 

basin covers available for use 

with either fiberglass or concrete 

basins. Basin hatch type covers 

are available in either steel or 

aluminum construction. The 

basin cover frame is designed to 

allow for mounting of rail support 

brackets.
Basin Bottom:

All cement pipe basins must have 

a smooth level troweled bottom 

for level mounting of discharge 

casting.
Level Sensing Controls:

Intrinsically safe type float 

controls are recommended for 

all applications and required for 

hazardous location/nonsparking 

service. An intrinsically safe 

control panel relay will limit the 

current and voltage to the level 

controls. A Hydromatic control 

panel can be supplied with this 

type circuitry.
The float level controls maintain 

the basin sewage water level by 

controlling pump turn-on and 

turn-off levels.
 1. The lower turn-off control 

should be set so that the pump 

stops at approximately the 

top of the pump. Consult the 

factory for any settings below 

this point.

 2. The upper turn-on control 

should be set above the 

lower turn-off control. The 

exact height between the two 

controls is determined by 

the number of pump starts 

desired and the depth of basin. 

A maximum of 10 starts per 

hour should not be exceeded.

  3.  The override control is set at 

a specified height above the 

upper turn-on control.

  4.  The alarm control is set about 

6" – 12" above the override 

control.

 5. No control should be set 

above the inlet invert.

Valves:

It is recommended that all check 

valves and shut-off valves be 

mounted outside the sump in a 

valve box. (See typical drawing 

detail, Fig. 1.) Shut-off valves 

should be of the water works 

approved type with resilient 

rubber disk seat.
CAUTION: After the pump 

is installed and sewage has 

entered the basin there is 

danger.  Sewage water gives off 

methane and hydrogen sulfide 

gases, which are poisonous. 

Never enter a wetwell unless 

proper confined space entry 

procedures are followed.

Installing Rail 

System Parts

(Fig. 3)
Mounting Cover, Discharge 

Base and Rails:

  1.  Set concrete cover with hatch 

opening in position.

 2. Bolt top rail support plates 

(Fig. 4) to hatch frame. The 

plate has slots so the two 

plates in a duplex system 

can be adjusted to obtain 

 

required center-to-center 

distance between pumps.

  3.  Lower the base or base/elbow 

assembly into the basin.

 4. Position the base elbow 

assembly by dropping a 

plumb line from center of 

pipe supports, located on top 

rail support plate, to center 

of tapered pins protruding 

from the top of the base elbow 

assembly. Level the elbow 

flange in two directions, 90° 

to each other. Shims may 

be required under the base 

in order to obtain this level 

condition. Mark the position 

of the base hold-down bolts 

through the holes in the base.

  5.  Move the base aside to allow 

drilling of the concrete for 

3/4" expansion bolts, 2-1/2" 

long. Move the base over the 

bolt holes and recheck with 

level and plumb line. Install 

expansion bolts.

  6.  Cut the pipe guide rails to the 

proper length and install them 

between the pipe supports at 

the top of the basin and pins 

on the base. Guide rails are 

Schedule 40, galvanized or 

stainless steel.

 7. Install discharge pipe as 

required by the particular job 

specifications.

  IMPORTANT: Discharge 

pipe and guide rails must 

be parallel if intermediate 

guide bracket is used.

 8. If the top rail support plate 

cannot be attached to the 

hatch cover frame, a special 

rail bracket (Fig. 5) can 

be furnished for mounting 

directly to a pipe cemented in 

the basin wall. This bracket is 

Содержание HYDROMATIC TL23HH

Страница 1: ...his manual to the owner of the equip ment or to the responsible party who maintains the system TL HIGH HEAD 2 1 2 4 DISCHARGE LIFT OUT GUIDE RAIL SYSTEM INSTALLATION AND SERVICE MANUAL Item E 03 496 P...

Страница 2: ...he locating pins and all fasteners are made of 300 series stainless steel Gaskets are constructed of neoprene rubber material The elbows are constructed of ASTM A48 Class 125 cast iron The hazardous l...

Страница 3: ...ove the inlet invert Valves It is recommended that all check valves and shut off valves be mounted outside the sump in a valve box See typical drawing detail Fig 1 Shut off valves should be of the wat...

Страница 4: ...ng Air tends to trap in the pump volute when water rises in the sump or when the pump is lowered into water after service To vent off this air a small hole is drilled into the pump volute Be sure this...

Страница 5: ...073A001 25073A001 25073A001 25073A001 25073A001 25073A001 5 Plate Guide 1 25072C000 25072C000 25072C000 25072C000 25072C000 25072C000 25072C000 7 Stud 4 05659A103 05659A103 05659A103 05659A103 05659A1...

Страница 6: ...Control Cords not shown Top Rail Support bolts to cover frame Hinged Access Door Alum or Steel Service Pole Option Opt Junction Box Must be used if control box is offset from basin Inlet Pipe size as...

Страница 7: ...Rail Support Fig 4 Chain Assembly Bottom of basin must have smooth troweled surface Base Disch Pin Guide Screw Set Cover Frame Guide Rails by others 2 Pipe Sch 40 Intermediate Guide Bracket as req d...

Страница 8: ...8 TOP RAIL SUPPORT Fig 4 Fig 5...

Страница 9: ...9 INTERMEDIATE GUIDE BRACKET U Bolt Part No IGB 2 3 24966D009 IGB 2 4 24966D010 IGB 2 6 24966D011 Fig 6...

Страница 10: ...RC S4HRCX M2 60 4 4 28 48 12 10 11 5 1 63 13 8 6 28 48 12 10 11 5 1 63 16 11 8 RTF RTF RTF RTF RTF RTF RTF RTF S4M S4MX H4H_H4HX 1PH H4H_H4HX 3PH S4LRC S4LRCX M2 60 4 4 30 48 12 10 11 5 1 63 13 8 6 30...

Страница 11: ...0 11 5 0 38 6 28 24 10 10 11 5 0 38 8 RTF RTF RTF RTF RTF RTF S4M S4MX H4H_H4HX 1PH H4H_H4HX 3PH S4LRC S4LRCX M2 48 4 4 30 24 10 10 11 5 0 38 6 30 24 10 10 11 5 0 38 8 RTF RTF RTF RTF RTF RTF S4NRC S4...

Страница 12: ...and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maint...