background image

5

TESTING  

After installation, unplug the 

 

primary sump pump and fill the 

sump with water. This is actually 

imitating the condition that would 

happen if the power went off  

or the primary pump failed for 

whatever reason. The back­

up sump pump should begin 

 

operation as the water level rises 

just above it’s top. If not, the  

float sensor may need to be 

 

re­positioned, review float 

 

in stal la tion  instructions.  Even 

after the back­up has pumped the 

excess water out and shut off, the 

alarm should continue sound ing 

until the ALARM switch is set to 

the OFF position. 

The alarm con tin ues to sound 

until the ALARM switch is set to 

OFF to alert you that something 

is wrong with the primary sump 

pump.

If the back­up pump operates 

properly, plug in the primary 

sump pump and set the ALARM 

switch ON and press the RESET 

button. The back­up system is 

now in full readiness.

If the back­up pump does not 

operate as specified, refer to the 

most asked questions list.

OPERATION

When the FLOAT SWITCH turns 

the back­up pump ON, the alarm 

buzzer will sound. When the 

FLOAT switch turns the backup 

OFF, the buzzer will con tin ue to 

sound until the ALARM switch is 

pushed to the OFF position. Push 

the ALARM switch to the ON 

position. Press the RE SET button 

for normal operation.

If the voltage of the battery drops 

lower than 11 volts DC, the LOW 

battery indicator will come on 

and the buzzer will sound if the 

ALARM switch is in the ON  

position. At this time, the battery 

should be checked and serviced or 

replaced. The only “real” test for a 

battery is when it is tested with a 

load meter. Take the battery back 

where it was pur chased for the 

test.  The CHARGING indicator 

will come ON when the battery is 

UNDERCHARGED.

The  CHARG ING  in di ca tor  will 

turn OFF when the DC voltage is 

over 13 volts, then the CHARGED 

indicator will come ON. At this 

time the battery is at FULL­

CHARGED condition and will 

stop charging. 

FG-A1 Testing 

and Operation

The CHARGED in di ca tor will be 

ON until the DC voltage drops. 

The battery will start charging 

again and the CHARG 

ING 

 

indicator will come ON. If either 

CHARGING  in di ca tor  and 

CHARGED indicator are not 

ON, check the charger adapter for 

proper connection.

Near the end of the CHARGING 

cycle, the CHARG 

ING and 

CHARGED indicators may 

 

alternately blink. If the lights 

blink  con tin u ous ly,  check  the  

battery leads for proper polarity 

(Step 4) and re place the fuse.

Press PUMP TEST switch for 

pump function test: the pump 

comes ON and ALARM in di ca tor 

comes ON and BUZZ ER sounds. 

Release the PUMP TEST switch, 

the pump turns OFF but the 

BUZZER con tin ues to sound and 

ALARM indicator continues to be 

ON. Press the RE SET switch, the 

BUZZER  and  ALARM  in di ca tor 

light will turn OFF. 

Figure 3  AC-115 V Outlet and 

Hydromatic piggyback switch plug

Содержание HYDROMATIC FG-A1

Страница 1: ...tic COM PH 888 957 8677 UNIT Installation and Service Manual FG A1 12 Volt Battery Back Up Power Supply 2013 Pentair Ltd All Rights Reserved W 03 435 Rev 03 04 13 NOTE To the installer Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system ...

Страница 2: ...well ventilated area 4 Battery must not be exposed to any sparks or flames An explosion or fire could result 5 Battery acid is very corrosive avoid spilling on skin or clothing Eye protection must be worn when handling the battery 6 Battery Selection and Maintenance Use a new 12 volt fully charged battery with top terminals For maximum performance and battery life a deep cycle marine group 24 min ...

Страница 3: ...ry indicator light will come on and the buzzer sounds for the ALARM function Battery should be checked by a battery shop 5 Assemble back up pump a minimum of 1 above the primary pump and tilt 30 per Figure 1 below The enclosed pump includes a built in check valve and screws directly into the side of the tee included The other two ends of the tee will accept 1 1 4 or 1 1 2 PVC and ABS pipe An addit...

Страница 4: ... reaches the bottom of the back up pump If not raise the float switch slightly Press the RESET and plug the primary sump pump back in Note Be sure that there is a 4 minimum from the top of the back up pump to the top of the sump The float switch should turn this pump ON near the top of the pump and at least 2 down from the top of the sump CONTROL PANEL BATTERY BOX BATTERY CHARGER RIGID 1 1 4 or 1 ...

Страница 5: ...attery drops lower than 11 volts DC the LOW battery indicator will come on and the buzzer will sound if the ALARM switch is in the ON position At this time the battery should be checked and serviced or replaced The only real test for a battery is when it is tested with a load meter Take the battery back where it was pur chased for the test The CHARGING indicator will come ON when the battery is UN...

Страница 6: ...kup pump activated and drained the tank The alarm activates any time the pump is called to op er ate It continues to operate until the alarm condition is manually acknowledged by press ing the reset switch Q Pressing the reset switch didn t silence the alarm Now what A The alarm circuit is activated so long as the float switch is activated Check to see if the backup float switch is tangled or caug...

Страница 7: ...p pump be used with a ped es tal sump pump A Yes However your sump basin must be at least 18 in diameter and an ad di tion al piece of PVC pipe must be used to extend the pump tee so the backup pump will not interfere with the float rod of the pedestal pump Q The pump is buzz ing but not pump ing What s wrong A There are several reasons why this situation might occur A The system is air locked Mak...

Страница 8: ... be accepted if received after the Warranty Period has expired This warranty is not transferable EXCEPTIONS Hydromatic Special Application Pumps Battery Back Up Sump Pumps Filtered Effluent Pumps Grinder Pumps and 2 1 2 Sewage Pumps are warranted for a period of 12 months from date of purchase or 18 months from date of manufacture whichever comes first HYDROMATIC SHALL NOT BE LIABLE FOR ANY CONSEQ...

Отзывы: