4
FG-A1
Installation
8. Insert the plug of the pump into the PUMP socket of the control panel.
9. Push the RESET button and the unit is ready for operation.
10. The backup sump pump should be checked by unplugging the primary sump pump and filling the sump
basin with water. When the water level is slightly above the backup sump pump it should turn on. As
the water level drops, the backup sump pump should turn off before the water level reaches the bottom
of the backup pump. If not, raise the float switch slightly. Press the RESET and plug the primary sump
pump back in.
Note: Be sure that there is a 4" minimum from the top of the backup pump to the top of the sump.
The float switch should turn this pump ON near the top of the pump and at least 2" down from the top
of the sump.
CONTROL PANEL
BATTERY BOX
BATTERY CHARGER
RIGID 1-1/4" or 1-1/2" PVC or ABS DISCHARGE
PIPE (NOT INCLUDED)
SUMP BASIN
CHECK VALVE
(NOT INCLUDED)
PRIMARY SUMP PUMP
(NOT INCLUDED)
TEE ADAPTER
FLOAT SWITCH
BACK-UP SUMP PUMP
(WITH BUILT-IN CHECK VALVE)
(TILT PUMP 30°)
4 INCHES MINIMUM
1 INCH MINIMUM
1-1/4" TETHER