5
Step 3:
Screw the metallic support frame to the
in-wall box
Step 4:
Install the floor sensor (mandatory for floor
sensing mode or room sensing mode with floor
temperature limiter). The floor sensor should be
installed in a separate flexible conduit all the way
to the end, covering the end of the sensor, for easy
replacement and to avoid possible signal disturbance
on the sensor. For best control performance, position
the floor sensor between two heating cables as close
as possible to the top floor surface.
Do not position the floor sensor tip closer than 3 cm to
the heating cable.
The floor sensor cable can be extended up to 100 m
with a separate standard installation cable 2 x 1.5 mm
2
(230VAC).