INSTALLATION AND OPERATION MANUAL – OWNER'S RECORD FFA MANUAL – FILTER FAILURE ALARM
8.1.2 User Menu – Settings Screen
The basic settings are displayed in the order they are shown on the Settings screen:
Figure 11: User Menu – Main Settings screen
1) SCALE
3) ALARM 2 (EARLY WARNING)
5) TIMER
2) SMOOTHING
4) ALARM 1 (HIGH ALARM)
6) SMOOTHING 4–20 mA
8.1.3 Changing Basic Settings
For other settings and functions refer to Advanced Settings below.
OPTION
SETTING
VALUES
DESCRIPTION
1
Scale
1–5, 10, 15, 25, 50, 75, 100,
125 … 950
Multiples of x. Changes the scale to adjust the sensor
sensitivity.
2
Smoothing
1, 2, 5, 10, 30, 60, 90, 900
Sets the number of samples used for the calculation of the
average output value (shown on the bar).
3
Alarm 2
(Early Warning alarm)
Incr5
Percentage. Sets the threshold for the early warning alarm.
This value cannot be greater than Alarm 1.
If the alarm is set to 0, it is disabled.
4
Alarm 1
(High alarm)
Incr5
Percentage. Sets the threshold for the high alarm.
Note:
adjusting this alarm setting may affect Alarm 2; ensure
that the alarms are set at the correct level.
5
Timer
1, 3, 10, 30, 60, 300, 600
Alarm delay, in seconds.
6
4–20 mA Smoothing
1, 2, 5, 10, 30, 60, 90, 300
In seconds. Changes the number of samples used
for the calculation of the average output value for the
4–20 mA interface.
8.2 ENGINEERING FUNCTIONS
8.2.1 Advanced Settings
The advanced settings are shown in the order they are accessed on the
Engineering
screen (see also Main Screens
on page 22):
Figure 12: Engineering Menu screen
1) USER PIN
3) 4 mA TRIMMING
5) FACTORY RESET
4
mA
2) UNLOCK FEATURES
4) 20 mA TRIMMING
6) SOFTWARE VERSION
20
mA
8.2.2 Changing Advanced Settings
OPTION
SETTING
VALUES
DESCRIPTION
3
4
4 mA trim
20 mA trim
±5%
of factory setting
Set trim using digits from 0–9. Values outside the boundaries are
ignored.
8.2.3 Factory Reset
1. Open the
Engineering
screen (see Main Screens on page 22).
2. Select Option 5
then select the green tick
to initiate the factory reset (or select the red
Fail
icon to cancel
the procedure).
The screen now displays
System init…
3. When the factory pre-sets have been restored, the control unit will restart automatically.
Содержание Goyen Mecair FFA
Страница 6: ......
Страница 40: ...34 INSTALLATION AND OPERATION MANUAL OWNER S RECORD FFA MANUAL FILTER FAILURE ALARM NOTES...
Страница 41: ...35 INSTALLATION AND OPERATION MANUAL OWNER S RECORD FFA MANUAL FILTER FAILURE ALARM NOTES...
Страница 42: ...36 INSTALLATION AND OPERATION MANUAL OWNER S RECORD FFA MANUAL FILTER FAILURE ALARM NOTES...
Страница 43: ...37 INSTALLATION AND OPERATION MANUAL OWNER S RECORD FFA MANUAL FILTER FAILURE ALARM NOTES...