dP Units *
Press Select
when the ‘dP Units’ LED is lit.
This LED should start to flash indicating it is in programming mode.
Use the Up
and Down
buttons to select a the dP Units in either
kPa or InWG.
Press Select
to confirm the setting. The ‘dP Units’ LED should now be lit.
Press Down
to scroll down the list.
High dP Alarm *
Press Select
when the ‘dP Units’ LED is lit.
This LED should start to flash indicating it is in programming mode.
Use the Up
and Down
buttons to set the value that will trigger
the High dP Alarm in the event the dP rises above this setting.
(Min. 00.0–Max. 18.0)
Press Select
to confirm the setting. The ‘High dP Alarm’ LED should
now be lit.
Press Down
to scroll down the list.
On Time
Press Select
when the ‘On Time’ LED is lit.
This LED should start to flash, indicating it is in programming mode.
Use the Up
and Down
buttons to select an On Time in
miliseconds between 30 ms and 990 ms, in increments of 10 ms.
Press Select
to confirm the setting.
Note: A standard setting is 150–250 ms.
Note: The Off Time must allow each solenoid to have a 60-second rest between
pulses.
PRODUCT INSTALLATION INSTRUCTIONS
GOYEN IS/ISP SERIES CONTROLLER
DEINE-012
PAGE 3 of 24
©COPYRIGHT Goyen Controls Co. Pty. Ltd.
Off Time
Press Select
when the ‘Off Time’ LED is lit.
This LED should start to flash, indicating it is in programming mode.
Use the Up
and Down
buttons to select an Off Time in seconds
between 1 s and 999 s.
Press Select
to confirm the setting.
Note: The Off Time must allow each solenoid to have a 60-second rest between
pulses.
Blowdown Cycles
Press Select
when the ‘Blowdown Cycles’ LED is lit.
This LED should start to flash, indicating it is in programming mode.
Use the Up
and Down
buttons to select the number of blowdown
cycles you require, between 0 and 10.
Press Select
to confirm the setting.
Note: Blowdown cycles can only be triggered by the Fan Stop Input.
Run
Press Select
when the ‘Run’ LED is lit.
This will automatically exit Programming Mode and save your settings.
WARNING: This installation must be performed by a
technically competent person. To prevent injury, damage
or malfunction, read the following intructions carefully.
If in doubt, contact your representative for further advice
* ISP only
ENGLISH