Fairbanks Nijhuis™

11/12/12

Intelliboost™ Water Booster System

Basic Operation Manual

5

Timed Pump Rotation by Hours of Operation.

 Lead pump changed to next pump when Hours of Operation Timer is 

timed out. Lag pump turns on and off as called for. Lag pump sequence is first Lag pump on, first Lag pump off. 

 

Same Lead Pump for All Starts.

 Same Lead pump turns on for every start. Lag pump turns on and off as needed. 

The Lag pump sequence is first Lag pump on, first Lag pump off. Transducer Failure Settings, when in Auto mode: 

Select Alarm or Fault. Alarm will allow continued operation when system is in Auto Mode and will run at Speed 

entered in the Alarm Speed Setting in Hz. If no flow is 

detected, drives will stop. Periodic starts will determine  

if flow is established. Fault will stop all drives.

Password Setup Disabled/Enable. When password Enabled, 

enter up to (4) numbers and record new password/pin. When 

enabled, Password screen will display if Menu button is 

pressed on Home screen. Factory Setting – Disabled.

Screensaver: To set Screensaver, select ON and input 

minutes of inactivity (minimum 2). Return from Screensaver by 

touching screen. Home screen will appear by default. Factory 

Setting – OFF.

Review Selections. If selections need adjusting, use Back or 

Start Basic Setup Over button. Press Finish when done, Home 

screen will display. 

Basic Setup finished. Set drives to Auto On, system now 

operational.

ADVANCED MENU:

Factory Set: Hardware, Speed Max/Min, Start/Stop, Discharge, 

Suction, Flow.

Advanced Menu Password/Pin – Factory Setting Default – 

Enabled, Password/Pin: 999.

ADVANCED SETUP:

If Password Protection for Advanced Menu is enabled, 

Password Entry Advanced screen will display when Advanced 

Содержание FAIRBANKS NIJHUIS INTELLIBOOST 7710 Series

Страница 1: ...sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system 7710 SERIES INTELLIBOOST WATER BOOSTER SYSTEM BASIC OPERATION MANUAL Part FM 03 554 201...

Страница 2: ...of communication will stop drive after Timeout Each drive shares the same parameter set except where drive name is required Drive1 2 Drive2 3 Drive3 4 Drive4 5 A Master Local Control Panel LCP is used...

Страница 3: ...Audio Visual indication set to Relay 1 May be enabled or disabled by touching Horn Lt R1 Home screen is the default screen Period of inactivity will display a screensaver if enabled by user No entrie...

Страница 4: ...turned on Other pumps that follow are Lag pumps Lead pump will turn on when minimum PSI is not met and Lead pump Time Delay is timed out Staging on of the pumps once Lead pump is established is based...

Страница 5: ...ne if flow is established Fault will stop all drives Password Setup Disabled Enable When password Enabled enter up to 4 numbers and record new password pin When enabled Password screen will display if...

Страница 6: ...Control Panel at VFD Drive screens monitor basic Drive Parameters Speed in Hz and VFD On Off VFD must be in Auto Mode for this screen operation In case of transducer failure Manual Control will be swi...

Страница 7: ...charge Alarms and Faults Alarms are set values to warn of conditions that may be harmful or undesirable for system Alarms Reset when system returns to desired operational values Alarm is recorded in N...

Страница 8: ...led for continued operation EQUIPMENT MAINTENANCE ALARM BASED ON HOURS OF OPERATION AND STARTS Alarm set to be indicated on Home screen Disable Alarms enter 1 at default Maintenance indicator will als...

Страница 9: ...larms is a set value not to be exceeded If exceeded within a set time period a Fault will occur and system will stop operating Fault restart requires Operator assistance Fault must be cleared or disab...

Страница 10: ...40 VAC 50 60 Hz Operator Controls Power Off On Switch Operator Touch Screen 5 7 Color Touch Panel Audible Visual Alarm Control Connections RS485 communication port to VFDs Discharge Pressure Transduce...

Страница 11: ...working on the pump Make sure that the power is locked out and that the pump cannot be accidentally started NOTICE Under no circumstances should the pump be operated without flow through the pump Nev...

Страница 12: ...ing guard 3 Verify that the electrical connections are in accordance with the wiring diagram on the motor 4 If the fan is visible turn on and off to verify rotation 5 To reverse the direction of rotat...

Страница 13: ...regreasing provisions Service Conditions NEMA Frame Size 140 180 210 360 400 510 1800 RPM and less Over 1800 RPM 1800 RPM and less Over 1800 RPM 1800 RPM and less Over 1800 RPM Standard 3 years 6 mon...

Страница 14: ...Low voltage at peak times 4 Motor starter has not tripped out but the motor does not run A Power failure B Fuses blown C Main contacts in motor starter are not making contact or the coil faulty D Con...

Страница 15: ...ause excess heat build up short circuits erratic drive operation and even component damage c This should be done after the installation of the drives is complete and before power is applied to the dri...

Страница 16: ...reapplied the fans should start and run for a few seconds d Listen for unusual noises from the fans when they are running e The VLT drives use a heat sink temperature sensor to help indicate if there...

Страница 17: ...Fairbanks Nijhuis 11 12 12 Intelliboost Water Booster System Basic Operation Manual 17 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 18: ...Fairbanks Nijhuis 11 12 12 Intelliboost Water Booster System Basic Operation Manual 18 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 19: ...19 Fairbanks Nijhuis 11 12 12 Intelliboost Water Booster System Basic Operation Manual THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 20: ...THIS PAGE LEFT BLANK INTENTIONALLY...

Отзывы: