Electrical Connections

General Information

Wiring connections must be made exactly as shown in the wiring diagram found on the inside of 

the heat pump access panel; see the wiring diagrams on pages 31-33.

The UltraTemp

TM

 Heat Pump must include a definite means of grounding and bonding. There is a 

ground lug inside the heat pump electrical compartment.

Equipotential Bonding

The Wiring Rules (AS/NZS 3000) and most other codes require in many circumstances that me-

tallic components of a pool structure, including reinforcing steel, metal fittings, and above ground 

equipment be bonded together with a solid copper conductor. The heat pump contains a metal (ti-

tanium) heat exchanger which is in contact with the pool water, which may need to be connected to 

this bonding grid. A bonding lug is provided to ensure this requirement can be met. Please refer to 

the Wiring Rules (AS/NZS 3000) and any local codes for details on whether equipotential bonding is 

required.

Main Power

Electrical wiring to the heat pump must be in accordance with the latest edition of the Wiring Rules 

(AS/NZS 3000). All wiring must be done by a certified or qualified electrician.

The following is the procedure to wire the heat pump to the electrical source:

Be sure the power to the circuit for the heat pump is turned off.

1. Remove the front panel of the heat pump cabinet (you need to loosen the front screws on the top 

panel aswell).

2. Remove the service panel to the heat pump electrical compartment. 

3. Electrical supply lines must be run through watertight conduit on the front panel. Run the wires 

and conduit from the power source and connect them to the conduit connection. Use suitable 

gauge connection wire as per below table.

4. Connect the power leads to the terminals in the electrical compartment as shown in the wiring 

diagram.

5. Verify that all other wires are secure, they may have loosened during shipment.

6. Connect the ground wire to the ground lug provided.

7. Replace the service panel and reinstall screws to hold it in place.

8. Replace the front panel.

Heat Pump

Cable Size

9.5kW

10A Plug and Cable Provided

12kW

15A Plug and Cable Provided

15kW

3 x 2.5mm

2  

(A, N, E)

17kW

3 x 4mm

(A, N, E)

21kW

3 x 6mm

(A, N, E)

Installation

Содержание eco select UltraTemp HX 12kW

Страница 1: ...r with the correct installation or operation of this type of equipment you should contact the distributor manufacturer for the correct advice before proceeding with the installation or operation of th...

Страница 2: ...products available When you see the Eco Select brand on one of our products you ll know it is our greenest and most efficient product in that equipment category These products do the best job of savin...

Страница 3: ...tinued 18 Setting the Clock 19 Setting the Timer 19 Menu Setting Parameters 20 Menu Query Parameters 21 Heating Cooling Mode 22 Forced Defrost Mode 22 Connecting the Heat Pump to Automation 23 To conn...

Страница 4: ...ings and cautions in this manual DANGER Risk of Electrical Shock or Electrocution This product must be installed by a licensed electrician Installations must comply with The Wiring Rules AS NZS 3000 A...

Страница 5: ...be carried out as per the instructions in this manual Failure to do so could result in water damage to property WARNING Cleaning the Unit To prevent injury always shut the power OFF when cleaning or s...

Страница 6: ...tanium heat exchanger The advanced titanium heat exchanger guarantees a longer life span free of corrosion It can be used with all types of water treatment including chlorine iodine bromine and salt w...

Страница 7: ...with the minutes 3 Set Timer Press TIMER CLOCK to enter into Timer setting interface Press UP HEAT COOL and DOWN DEFROST to select the timer number T1 or T2 Press TIMER CLOCK to modify timer Use UP HE...

Страница 8: ...p HX 9 5kW and 12kW units UltraTemp HX 15kW 17kW and 21kW units A 657mm 757mm B 945mm 1125mm C 159mm 181mm D 620mm 750mm E 366mm 446mm F 417mm 490mm G 96mm 86 5mm H 370mm 455mm Dimensions Dimensions S...

Страница 9: ...tary Rotary Scroll Compressor Brand Toshiba Toshiba Panasonic Water Flow m3 hr LPM 5 19 87 6 1 102 14 233 Refrigerant R410A 1 3kg R410A 1 5kg R410A 1 8kg Description UltraTemp 17kW UltraTemp 21kW Part...

Страница 10: ...pad is pitched not more than 20mm per metre in any direction as needed for runoff Drainage and Condensation Condensation occurs from the evaporator coil while the unit is running and drains at a stea...

Страница 11: ...gh solid fence or other permanent barrier 4 Install heat pump a minimum of 250mm from the wall of the house 5 Allow 600mm clearance above the heat pump for service access SLAB 1 5m min CLEARANCE EVAPO...

Страница 12: ...chor and tighten to secure the clamp and heat pump to the equipment pad 250mm min 250mm min 250mm min 1 5m min Clearance HEAT PUMP ANCHOR CLAMP BOLT ANCHOR installer provided HEAT PUMP BASE 1 3 8 HEX...

Страница 13: ...the water flow which passes through the heat pump and to isolate the heat pump com pletely for any maintenance work without cutting the filtration flow If your installation is equipped with water tre...

Страница 14: ...r any combination of heat sources including solar All heat sources must be plumbed in series to work correctly and efficiently A recommended plumbing layout for a heat pump heater solar combination he...

Страница 15: ...heat pump must be in accordance with the latest edition of the Wiring Rules AS NZS 3000 All wiring must be done by a certified or qualified electrician The following is the procedure to wire the heat...

Страница 16: ...inued Figure 7 Location of Electrical Panel Connect Power Here L Active N Neutral and Earth Optional Pump P1 240V Active input from supply P2 240V Active output to pump Automation control input Figure...

Страница 17: ...on will show if the UltraTemp is on and is in Cooling mode The UltraTemp will cool the water until the set temperature is reached 3 Set Temperature This shows the set temperature Press the UP DOWN but...

Страница 18: ...19 for further details 10 MENU SET MENU SET Press once to query current running parameters and error code display Hold for 5 seconds to access parameter settings menu Refer to Page 20 for further det...

Страница 19: ...er setting interface 2 Then press UP HEAT COOL and DOWN DEFROST to select the timer number There are 2 separate on off Timers 3 When Timer 1 is flashing press TIMER CLOCK to enter into Timer 1 ON hour...

Страница 20: ...ess ON OFF UNLOCK at any time to confirm settings and go back to main interface Code Parameter Name Description Range Default L2 Temperature Differential Set how much the water temperature needs to dr...

Страница 21: ...perature at the inlet of the compressor 10 150 C Heat 10 250 C Cool A3 Compressor exhaust gas temp This is the refrigerant gas temperature at the outlet of the compressor 40 800 C Heat 60 950 C Cool A...

Страница 22: ...ode 1 Icon for Heating mode Icon for Cooling mode Figure 10 Heating Cooling Mode Icons Forced Defrost Mode 1 When the unit is on hold DOWN DEFROST for 5 seconds to enter into forced defrosting mode 8...

Страница 23: ...Spa Heating Combinations Recommended Configurations Heat Sources Connections EasyTouch Configuration Heat Pump Only Connect heat pump to 2 wire ter minal marked Gas Heater J19 Menu Heat Menu Pool Temp...

Страница 24: ...2 core 1mm2 cable to heat pump REMOTE terminals Solar Connect to Relay for Solar Pump for seperate solar pump system AUTOMATION WIRING FOR HEAT PUMP SOLAR Connect 2 core 1mm2 cable to Gas Heater s FIR...

Страница 25: ...i tute Inspection and Service Pentair Heat Pumps are designed and constructed to provide long performance life when installed and operated properly under normal conditions Periodic inspections are imp...

Страница 26: ...s used Equally important are the environmental conditions for example air temperature humidity water temperature and wind To maintain maximum performance and efficiency keep the air coil clean from di...

Страница 27: ...and heat exchanger must be cleaned by a technician Use only pressurized drinking water for cleaning Cleaning the air system The finned heat exchanger fan and condensate outflow should be clear of all...

Страница 28: ...correct set point tempera ture has been set The set temperature level cannot be reached Please check whether The permissible operating conditions for the heat pump have been adhered to air tempera tu...

Страница 29: ...onnection of pres sure switch 4 Pressure switch failure 5 Main PCB damaged 1 Add some refrigerant 2 Replace the capillary 3 Reconnect the switch 4 Replace the pressure switch 5 Replace the PCB Er09 Co...

Страница 30: ...circuit 3 Main PCB damaged 1 Check the sensor con nection 2 Replace the sensor 3 Replace the main PCB Er35 Compressor high current protection 1 Inadequate water flow rate under heat mode 2 If ambient...

Страница 31: ...TROLLER 27 803114 GRILL 9kW 12kW Item Part No Description 27 803153 GRILL 15kW 17kW 21kW 28 803115 FRONT PANEL 9kw 12kW 28 801328 FRONT PANEL 15kW 17kW 21kW 29 30 803117 FAN BLADE NUT 9kW 12kW 29 30 8...

Страница 32: ...Page 32 Appendix Wiring Diagrams Wiring Diagram UltraTemp 9 5kW 12kW 15kW models...

Страница 33: ...Page 33 Appendix Wiring Diagram UltraTemp 17kW 21kW models Wiring Diagrams Continued...

Страница 34: ...accordance with relevant local and national legislation Do not try to dismantle the system yourself the dismantling of the system treatment of the refrig erant of oil and other parts must be done by a...

Страница 35: ...Page 35 Notes...

Страница 36: ...entair com Web www pentairpool com au International Phone 61 3 9709 5800 Fax 61 3 9709 5888 2017 Information contained here in remains the property of Pentair Australia Pty Ltd Any reproduction displa...

Отзывы: