Figure 1. Heat-tracing control

Cir

cuit
1Cir

cuit
2

G

Ø

Ø

Heating

cable

Power

connection

Thermostat bulb

(see "Positioning"

instructions above

for mounting details)

Braid

Control

thermostat

Relay

GFEPD

Power supply

208-V or 240-V supply – 240-V heater

G

Ø

Ø

WIRING

INSTALLING THE THERMOSTAT

1.  Verify that the thermostat 

is suitable for the area 

where it is to be installed. 

2.  Check the line voltage and 

the heat-tracing load to 

ensure that the thermostat 

ratings are not exceeded.

3.  Mount the unit using unistrut or the  universal mounting 

bracket (UMB-263757) in a position that prevents condensation 

from draining into the enclosure from the connecting conduit 

(see diagram above).

pOSITIONING THE SENSOR BULB 

4.  Position the bulb in the 

lower quadrant of the pipe 

as shown in the diagram 

to the left. Place the bulb 

at least three feet from 

pipe supports, valves, or 

other heat sinks; protect 

the capillary from kinks or 

bends less than 1⁄2 inch in 

radius. 

5.  Tape the bulb firmly to the pipe with AT-180 aluminum tape, 

making sure there is no air space between the bulb and pipe.  

Do not overlap the bulb and heating cable with the same piece 

of AT-180 tape.

6.  For metal-tank-wall sensing, use the BCK-35 bulb clamp 

(purchased separately from Pentair Thermal Management) 

and install the clamp per the instructions provided. Make sure 

there is no air space between the tank wall and the bulb. 

  For installation on plastic tanks, contact Pentair Thermal 

Management at (800) 545-6258.

SETTING THE THERMOSTAT

7.  Set the thermostat dial to the desired temperature, then finish 

wiring.

8.  Complete insulating. Do not turn the system on until the bulb is 

covered with thermal insulation.

9.  Fill the piping or tank. Once the thermostat has begun to cycle, 

check the fluid temperature with an immersed thermostat 

(best for plastic systems) or an accurate temperature indicator. 

Adjust the dial setting, if necessary.

Conduit

drain

90

Heating cable

Control thermostat bulb

AT-180 tape

AT-180 tape

Heating cable

Control thermostat bulb

Double traced

Single traced