MAINTENANCE INSTRUCTIONS

Copyright © 2013 Pentair

ANGMC-6026-US-1312

page 9

Engineering Doc. #05.9040.083 Rev. E

6.0  PILOT SET PRESSURE FIELD TEST PROCEDURE (REFER TO FIGURE 6)

This procedure is for measuring the pressure where the valve will open. It will not
measure where the valve closes. To measure the closing pressure, use the procedure in
Section 5.0.

6.1

Remove the pilot discharge tube from the pilot and replace with a cap that has 
a .06" diameter [1.5 mm] hole in it.

6.2

Connect the test equipment to the field test valve.

6.3

With the metering and vent valve closed, open the gas bottle and adjust the 
regulator pressure to about 200 psi [14 kp/cm

2

].

6.4

Open the field test valve. Slowly open the metering valve and observe the test
gauge. Increase the pressure until gas flow at the pilot discharge fitting increases
rapidly. The pressure at which this occurs is the set pressure of the valve.

6.5

To adjust the opening pressure turn the spring adjusting screw under the 
cap/adapter “IN” to increase pressure or “OUT” to decrease pressure.

6.6

The IMO (International Maritime Organization) Rule set pressure tolerances are:

+ 10%

0 - 21.3 psi [0 - 1.5 kp/cm

2

]

+ 6%

21.3 - 42.7 psi [1.5 - 3.0 kp/cm

2

]

+ 3%

42.7 psi or 3.0 kp/cm

2

and above

Type 95 pilot recommended field test set-up

Adapter fitting to

1

/

2

" NPT port on

field test valve

Primary set

pressure

adjustment

under cap

Nitrogen

bottle with

shutoff

valve and

regulator

Bonnet

vent
Pilot

Field

test

valve

Test gauge

Metering

valve

Auxiliary set

pressure

adjustment 

under cap

High

pressure

hose

Vent

valve

Unscrew here 

for removal 

(install hand-tight only –

lubricate threads)

Pilot

discharge

fitting

Auxiliary setter

Pilot

discharge

tube

Main valve

FIGURE 6

Содержание ANDERSON GREENWOOD 95 POSRV

Страница 1: ...tallation or maintenance of the product or the use of parts or components not manufactured by Anderson Greenwood may result in a failure of the product Any installation maintenance adjustment test etc...

Страница 2: ...eck valve Tank pressure sense line Main valve Unbalanced Piston Dome top of the piston Pilot vent Pilot Inlet tank pressure O ring seat Outlet TABLE OF CONTENTS 1 0 General valve description 1 2 0 Acc...

Страница 3: ...ighten the body bolts first one side then the opposite side Do not overtighten the bolts as this will distort the diaphragm and cause leakage NOTES 1 Gasket used on some check valves If check valve ha...

Страница 4: ...replace the seat The piston seal should not need to be replaced If the piston seal is removed a new seal must be installed The piston can be removed from the cap liner by pulling the piston out or by...

Страница 5: ...tightening will damage them Hold the hex spacer when torquing the spindle nut to prevent the stack from rotating After the pilot is assembled the set pressure must be adjusted Refer to Section 5 0 for...

Страница 6: ...ANDERSON GREENWOOD TyPE 95 POSRV MAINTENANCE INSTRUCTIONS page 6 ANGMC 6026 US 1312 Copyright 2013 Pentair Engineering Doc 05 9040 083 Rev E Type 95 pilot with auxiliary setter FIGURE 4A...

Страница 7: ...ANDERSON GREENWOOD TyPE 95 POSRV MAINTENANCE INSTRUCTIONS Copyright 2013 Pentair ANGMC 6026 US 1312 page 7 Engineering Doc 05 9040 083 Rev E FIGURE 4B...

Страница 8: ...e will decrease due to the pressure drop in the lines to the accumulator The set pressure is the highest pressure recorded on the supply pressure gauge 5 3 Decrease the supply pressure to the correct...

Страница 9: ...e test gauge Increase the pressure until gas flow at the pilot discharge fitting increases rapidly The pressure at which this occurs is the set pressure of the valve 6 5 To adjust the opening pressure...

Страница 10: ...preventer check valve leaks Item 15 Figure 2 Check for gas flow at discharge tube to main valve outlet No gas flow should be detected Valve opens at Pilot not sensing correct tank pressure correct pr...

Отзывы: