ANDERSON GREENWOOD
TyPE 95 POSRV
MAINTENANCE INSTRUCTIONS
Copyright © 2013 Pentair
ANGMC-6026-US-1312
page 3
Engineering Doc. #05.9040.083 Rev. E
2.0 ACCESSORY MAINTENANCE (REFER TO FIGURE 2)
The accessories used on the Type 95 are the auxiliary setter, field test and backflow
preventer. The field test and backflow preventer are always used; the auxiliary setter
is optional.
Only the backflow preventer, which consists of one
(2)
diaphragm type check valve and a
ball check valve requires maintenance. Normal maintenance is to clean the check
valves and replace the diaphragm, washer, gasket,
(1)
and O-ring.
When replacing the diaphragm, care should be taken not to damage the diaphragm. To
assemble the diaphragm type valve, uniformly tighten the body bolts, first one side, then
the opposite side. Do not overtighten the bolts as this will distort the diaphragm and
cause leakage.
NOTES:
(1)
Gasket used on some check valves. If check valve has gasket, use gasket
supplied in repair kit - otherwise discard kit gasket.
(2)
Some earlier model valves use two diaphragm check valves and no ball check valve.
ITEM
DESCRIPTION
* 1
Auxiliary setting device
2
Supply tubing
3
Pilot exhaust tubing
4
Pilot bracket bolt
* 5
Pilot
6
Pipe nipple
7
Field test hand valve
8
Field test plug
9
Connector
10
Check valve
11
Connector
12
Connector
13
Close tee
15
Check valve
16
Connector
17
Connector
18
Pipe plug
19
Body bolt
20
Lock washer
21
Upper body
* 22
Diaphragm
* 23
Washer
24
Spring pin
25
Lower body
26
Body
27
Spring
28
Ball
29
O-ring
(1)
30
Gasket
*
Recommended spare parts for repairs
Auxiliary setter, with field test and backflow preventer
indexed in order of disassembly
FIGURE 2